Installation manual

Maintenance
Cleaning the condensate receptacle
Cleaning and refilling the syphon
Inspection of combustion chamber
22
5
6
7
Cleaning the condensate receptacle
Disconnect the plug of the fluegas
temperature sensor (1);
Remove the internal fluegas pipe (2)
of the boiler in order to create access
to the condensate receptacle;
Clean the receptacle (3);
Mount the fluegas pipe back in
position when the cleaning is finished;
Connect the plug of the fluegas
temperature sensor.
Inspection of combustion chamber
The inspection opening is positioned on
the left hand side of the boiler.
Remove the radiation panel (5) from
the heat exchanger;
Remove the cover (6) from the
inspection opening;
Inspect the combustion chamber (7),
clean if necessary;
Mount the cover and radiation panel
back in original position.
Cleaning and refilling the syphon
Remove the syphon (4) from the
condensate connection;
Clean and fill it with fresh water;
Mount the syphon back in the original
position.
4
1
3
2