Installation manual

25
In case of a lockout, a warning triangle (E) and a flashing error code appears on the display. The cause of a fault should first
be determined and eliminated before the boiler is being reset. In case the lockout appears more than twice within 6 minutes or
maintains for longer than 6 minutes, the error code is added with a “
3
”. The table below shows all possible lockouts and an
indication of possible cause.
Lockouts
No. Error type Explanation Possible solution
1
Lockout Water flow temperature has exceeded the high
limit temperature setting (100ºC).
Check if boiler is in automatic mode (K), Check if water
flow through the boiler is sufficient, check if (P11+P12)
< High limit setting (V9).
2
Interlock Gas pressure has dropped below minimum value
of minimum gas pressure switch or additional
safety device connected to the interlock input has
been interrupted (during startup).
Check gas supply pressure / check function of
additional safety device on interlock input.
3
Interlock Gas pressure has dropped below minimum value
of minimum gas pressure switch or additional
safety device connected to the interlock input has
been interrupted (during operation).
Check gas supply pressure / check function of
additional safety device on interlock input.
4
Lockout No flame ionisation signal detected during burner
start.
Check phase/neutral of power supply (phase
sensitivity!), check gas supply, check ignition spark,
increase gas valve setting min. load (alan key screw).
5
Lockout Flame ionisation signal lost during operation. Check gas supply pressure during operation, check
gas valve setting via combustion analysis.
6
Interlock Water flow temperature has exceeded the
temperature limiter setting (97ºC).
Check if boiler is in automatic mode (F), check if water
flow through the boiler is sufficient, check if (P11+P12)
< Temp. limiter setting (V10).
7
Lockout Fluegas temperature has exceeded the high limit
temperature setting (100ºC).
Check if water pressure is sufficient, check if water
flow through the boiler is sufficient, check if heat
exchanger is clean (fluegas and water side).
11
Lockout Flame ionisation signal detected before burner
start.
Check ionisation electrode, measure ionisation current
when boiler is off, check wiring between ionisation
electrode and boiler controller.
12
Interlock Water flow temperature sensor is defective Check resistance of sensor (see chapter “sensor va-
lues”), check wiring between water flow temperature
sensor and boiler controller.
13
Interlock Fluegas temperature sensor is defective Check resistance of sensor (see chapter “sensor va-
lues”), check wiring between fluegas temperature sen-
sor and boiler controller.
14
Interlock DHW temperature sensor (optional) is defective Check resistance of sensor (see chapter “sensor va-
lues”), check wiring between DHW temperature sensor
and boiler controller.
15
Interlock Outside temperature sensor (optional) is
defective
Check resistance of sensor (see chapter “sensor va-
lues”), check wiring between outside temperature sen-
sor and boiler controller.
18
Interlock Header temperature sensor (optional) is defective Check resistance of sensor (see chapter “sensor va-
lues”), check wiring between header temperature sen-
sor and boiler controller.