Instruction manual

AC Test
If you do not have a signal generator, skip to
procedure 4.
Make sure that the power switch is in the OFF
position. Turn the squelch control fully
counterclockwise . Set the mulitmeter to read
20VDC full scale and connect to the circuit as
shown in Figure 21. Connect the positive voltage
probe to pin 13 of integrated circuit U1. Connect the
common probe to the negative lead from the battery.
AC couple a generator capable of producing a
455kHz signal to pin 5 and attach the generator
ground lead to the ground lead of the volume control
(see Figure 21). Set the generator frequency to
455kHz and the amplitude to between 50 and
100mV peak to peak. Turn the power ON. Turn coil
L5 to its maximum counterclockwise position. The
multimeter should read approximately 2.4V. Turn L5
slowly clockwise. The multimeter voltage should
rise to a maximum of about 3.0V, then fall to a
minimum of about 1.5V and then rise again. Record
the maximum (Vmax) and minimum (Vmin)
voltages. Set L5 midway between Vmax and Vmin.
For example, if Vmax = 2.95V and Vmin = 1.45V, set
L5 to (Vmax + Vmin)/2 = (2.95 + 1.45)/2 = (4.40)/2
= 2.2V.
A small increase in generator frequency (positive
deviation) should cause the DC voltage at pin 13 to
drop. Likewise, a small increase in generator
frequency (positive deviation) should cause the DC
voltage to rise. Careful point-by-point plotting (use
increments of about 1kHz) should reproduce a
curve similar to the one shown in Figure 16. If not,
turn the power OFF and check that the 455kHz filter
F1 is installed correctly. Also check for solder
shorts, unsoldered leads, and parts you may have
missed in the block 2 assembly instructions.
-17-
Figure 21
V
A
COM
V
104
455kHz
20A