Technical information

20
THERMAL MAPPING AND HEAT LOSS
CALCULATION IN THE UK
W/m
2
W/m
3
THERMAL LEVELS
HIGH
INSULATION
MEDIUM
INSULATION
LOW
INSULATION
HIGH
INSULATION
MEDIUM
INSULATION
LOW
INSULATION
MILD WEATHER 64 82,5 109 19,6 25,3 33,4
COLD WEATHER 69,5 88 114,5 22,5 28,6 37,2
VERY COLD WEATHER 75 93,5 120 26,4 33 42,3
EXTRA COLD WEATHER 80,5 99 125 29,5 36,3 45,8
The table below shows recommended
gures that will help to calculate the power
requirement in W/m2 or W/m3 to install
GABARRÓN Inertia Thermal Radiators.
The main variables for the calculation are
three optional types of insulation in the house
that have to be considered together with
different climatic zones in the UK.
To calculate the theoretical heat loss in a room
it is necessary to multiply the required gure
in the chart by the calculated room volume
or surface.We install the inertia thermal
radiator with the power immediately above to
theoretical power obtained.
In bedrooms and kitchens it is possible to
reduce the theoretical power required by 20%.
But in the same way, all rooms located in a
top oor would be recommended to increase
the theoretical power by 20% too.
These gures have been developed to get a
comfort temperature of 21ºC.
THERMAL INERTIA RADIATORS