Environmental:
Ambient temperature operation: -20°C to +55°C; storage: -40°C to + 85°C
Climatic conditions acc. to IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
Dust <1mg/m
Max. installation altitude ≤1500m
Audible noise ≤45dBA at 1m distance
Mechanical:
Type of construction 19’’- compatible rack acc. to DIN 41494
Cooling forced cooling with internal fan (temperature regulated; monitored)
Surfaces powder coating RAL 7035 (front panel only), black imprint; con-
structive parts: anodized metal
Dimensions (W/H/D) UNB 5kVA + 12.5kVA: 483/133/360mm (3HU)
UNB 23kVA + 30kVA + 40kVA: 483/177/460mm (4HU)
Weight UNB 5kVA + 12.5kVA: approx. 12.6kg
UNB 23kVA: approx. 13.2kg
UNB 30kVA: approx. 15.8kg
UNB 40kVA: approx. 16.9kg
Electrical connectors Front side: 2 x CAN-Bus (RJ11); 1 x Sub-Min-D9 connector (not used)
Rear side: AC inputs/output, DC input and signalization;
UNB 5kVA + 12.5kVA: 1 x HAN-K4/8; UNB 23kVA: 2 x HAN-K4/8;
UNB 30kVA + 40kVA: 3 x HAN-K4/8
Applicable standards:
Type of enclosure/protection class IP20 (front panel) /1 acc. to EN 60950 (electr.)
CE conformity yes
Compliance to EMC standards EN55011/55022 class “B”; EN61000-4 part 2-5)
Compliance to safety standards acc. to EN60950-1; VDO0100 T410; VDO0110; EN60146