User Guide

C-14E2 RX/BX/CX I&O Manual 026-1610 Rev 13 14-SEP-2011
User Cleared All Applications 50 A user has cleared out all data from all applications in
this E2.
User/Appl. Forced Reset 50 A user or an application has forced a reset of this E2.
VS Alarm 20 Multiflex PAK variable speed device alarm.
VS Inverter Fail User A variable-speed inverter driving a variable-speed
fan or compressor has failed.
WCC Controller Alarm 20 Woodley case controller alarm.
WPK Controller Alarm 20 Woodley Pack Amps Fail alarm.
Watchdog Countdown Hit Zero 20 E2 locked up while trying to perform a task. If this
alarm occurs often, there may be a problem with your
system. Contact Retail Solutions service.
Watchdog Reset Timer Failed 20 E2 tried to reset itself to clear a hung task, but the
“watchdog” feature on the E2 was disabled. Check
the jumper J19 labeled “Watch Dog” on the E2 main
board. This jumper should be either be set to
“ENABLE” or it should not be present at all.
X300<->X300 Links Lost-CRC Err 20 An internal error has caused a loss of communication
between E2s.
Alarm Name
Default
Priority
Definition