User Guide

The 16AI, 8IO, and MultiFlex Inputs Input and Output Setup9-3
P/N Sensor
Input Type
Dip Switch
Wiring
various Temp Sensors
and Probes
Up
1. Connect one lead to the odd
numbered terminal and the
other lead to the even num-
bered terminal (polarity
insensitive).
various Digital Sensors
(Klixons, Sail
Switches, etc.)
Up
1. Connect one lead to the odd numbered
terminal and the other lead to the even
numbered terminal (polarity insensitive).
800-2100
800-2200
800-2500
Pressure Trans-
ducers (CPC)
100, 200, 500
lb. ratings
(0.5-4.5VDC
output, 5VDC
input voltage)
Up
1. Connect RED power
wire to +5VDC sup-
ply on input board.
2. Connect WHITE sig-
nal wire to even num-
bered terminal.
3. Connect BLACK
ground wire to odd
numbered terminal.
4. Connect the bare
SHIELD wire to odd
numbered terminal.
203-5750 Relative Humid-
ity Sensor
Down
1. Wire the “P”
sensor terminal
to 12VDC sup-
ply on board.
2. Wire the
“GND” sensor
terminal to odd
numbered ter-
minal.
3. Wire the
“OUT” sensor
terminal to even
numbered ter-
minal.
4. Jumper sensor
terminal “N” to
sensor terminal
“GND”.
Table 9-1 - Sensor Wiring