Installation manual

Air Cooled Models
21
Figure 13 Piping: Fan speed control condensers
Table 9 Fan speed control condenser piping connection sizes - Cu OD
Condenser Model
Number
Entering Hot
Gas Line
In. (mm)
Returning
Liquid Line
In. (mm)
CDF-065 1/2 (12.7) 1/2 (12.7)
CDF-083L 1/2 (12.7) 1/2 (12.7)
CDF-086 7/8 (22.2) 1/2 (12.7)
CDF-097/107C 7/8 (22.2) 1/2 (12.7)
CDF-104L 7/8 (22.2) 1/2 (12.7)
CDF-130 7/8 (22.2) 5/8 (15.9)
CDF-165L 7/8 (22.2) 5/8 (15.9)
CDF-175 7/8 (22.2) 5/8 (15.9)
CDF-205L 1-1/8 (28.6) 7/8 (22.2)
CDF-217C/216C 1-1/8 (28.6) 7/8 (22.2)
CDF-251L 1-1/8 (28.6) 7/8 (22.2)
CDF-258 1-1/8 (28.6) 7/8 (22.2)
CDF-291 1-1/8 (28.6) 1-1/8 (28.6)
CDF-308L 1-3/8 (34.9) 1-1/8 (28.6)
CDF-330L 1-3/8 (34.9) 1-1/8 (28.6)
CDF-360/349C 1-3/8 (34.9) 1-1/8 (28.6)
CDF-415L 1-3/8 (34.9) 1-1/8 (28.6)
CDF-480C 1-5/8 (41.3) 1-1/8 (28.6)
CDF-510C 1-5/8 (41.3) 1-1/8 (28.6)
For runs longer than 150 feet (45.7m) equivalent length, con-
sult factory for proper line sizing.
Entering hot
gas line (Typ.)
Returning
liquid line (Typ.)
Inverted traps are to be field-supplied and installed (Typ.).
When installing traps, clearance must be provided for
swing of end access door. Traps are to extend above base
of coil by a minimum of 7-1/2" (190mm).