Installation manual

Air Cooled Models
22
Figure 14 Piping: Lee-Temp control condensers
Table 10 Lee-Temp control condenser piping connection sizes
Condenser Connections-ODS
inches (mm)
Lee-Temp
Size
Lee-Temp Connections-ODS
inches (mm)
Model # Hot Gas A Liquid B
Hot Gas
Tee F
Liq. to L-T
Valve C
Receiver
Out D
CDL-065 1/2 (12.7) 1/2 (12.7) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-083L 1/2 (12.7) 1/2 (12.7) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-086 7/8 (22.2) 1/2 (12.7) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-097 7/8 (22.2) 1/2 (12.7) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-104L 7/8 (22.2) 1/2 (12.7) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-130 7/8 (22.2) 5/8 (15.9) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-165 7/8 (22.2) 5/8 (15.9) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-175 7/8 (22.2) 5/8 (15.9) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-205L 1-1/8 (28.6) 7/8 (22.2) (2) W-4 1-1/8 (28.6) 7/8 (22.2) 5/8 (15.9)
CDL-217C 1-1/8 (28.6) 7/8 (22.2) (2) W-5 1-3/8 (34.9) 7/8 (22.2) 7/8 (22.2)
CDL-251L 1-1/8 (28.6) 7/8 (22.2) (2) W-4 1-3/8 (34.9) 7/8 (22.2) 7/8 (22.2)
CDL-258 1-1/8 (28.6) 7/8 (22.2) (2) W-5 1-3/8 (34.9) 7/8 (22.2) 7/8 (22.2)
CDL-291 1-1/8 (28.6) 5/8 (15.9) (2) W-5 1-3/8 (34.9) 7/8 (22.2) 7/8 (22.2)
CDL-308L 1-3/8 (34.9) 1-1/8 (28.6) (2) W-5 1-3/8 (34.9) 7/8 (22.2) 7/8 (22.2)
CDL-330L 1-3/8 (34.9) 1-1/8 (28.6) (2) W-5 1-3/8 (34.9) 7/8 (22.2) 7/8 (22.2)
CDL-360 1-3/8 (34.9) 1-1/8 (28.6) (2) W-5 1-3/8 (34.9) 7/8 (22.2) 7/8 (22.2)
CDL-415L 1-3/8 (34.9) 1-1/8 (28.6) (2) W-5 1-3/8 (34.9) 7/8 (22.2) 7/8 (22.2)
CDL-480C 1-5/8 (41.3) 1-1/8 (28.6) (2) W-6 1-3/8 (34.9) 1-1/8 (28.6) 7/8 (22.2)
CDL-510C 1-5/8 (41.3) 1-1/8 (28.6) (2) W-41 1-3/8 (34.9) 1-1/8 (28.6) 7/8 (22.2)
For runs longer than 150 feet (45.7m) equivalent length, consult factory for proper line sizing.
Entering hot gas line (Typ.)
Returning liquid line (Typ.)
Lee-Temp receiver tank
10061Pg6