Installation manual

Air Cooled Models
27
Figure 18 Outdoor air cooled 6 and 8 fan condenser cabinet and anchor dimensional data
Table 14 Outdoor air cooled 6 and 8 fan condenser physical data
Model
# of
Fans
ABCE L
CFM (l/s)
60 Hz
THR 60 Hz.
BTU/hr (kw)
CFM (l/s)
50 Hz
THR 50 Hz
BTU/hr (kW)
Net
Weight
lb (kg)
in
(mm)
in
(mm)
in
(mm)
in
(mm)
in
(mm)
-616L 6
122
(3099)
_
124
(3150)
59
(1499)
131-1/2
(3340)
31330
(14785)
23854
(12.6)
26108
(12320)
21056
(11.2)
1380
(627)
-660L 8
82
(2083)
80
(2032)
164
(4166)
70
(1778)
171-1/2
(4356)
48000
(22651)
26478
(14.0)
40000
(18875)
24412
(12.8)
1600
(727)
-830L 8
82
(2083)
80
(2032)
164
(4166)
70
(1778)
171-1/2
(4356)
43200
(20386)
31114
(16.4)
36000
(16988)
27366
(14.6)
1670
(759)
-960C 8
82
(2083)
80
(2032)
164
(4166)
70
(1778)
171-1/2
(4356)
50576
(23876)
35660
(18.8)
42146
(19888)
31926
(16.8)
2090
(950)
-1010C 8
82
(2083)
80
(2032)
164
(4166)
70
(1778)
171-1/2
(4356)
43400
(20485)
40344
(21.3)
36167
(17070)
35050
(18.5)
2640
(1198)
THR - Total Heat Rejection, 1°F TD, for Total Condenser
THR - Total Heat Rejection, 1°C TD, for Total Condenser (50 Hz)
Recommended rigging and spreader
bars required for installation; rigging
and bars not supplied by Liebert
Clearance of 36" (914.4mm) recommended
on all sides for proper operation and
component access
UNIT ANCHOR PLAN
TYPICAL FOOTPRINT
Condenser Physical data
Optional
disconnect
switch
handle
18"
(457mm)
Height to top
of fan guard
43-1/8"
(1095mm)
1/2" (12.7mm) diameter
anchor bolts (typ.)
4 legs furnished for
6-fan models
6 legs furnished for
8-fan models
37-7/8"
(962mm)
86-3/4"
(2203.5mm)
E
C
L
87-1/8"
(2213mm)
NOTE: Refer to
sheet 10067 Pg. 4
for connection
sizes
Location of holes and
support for rigging (typ. 4)
Center leg
provided on
8-fan models
only
Additional legs provided on condensers
with Lee-Temp receivers
1" (25.4mm)
4-1/4"
(108mm)
1-3/4"
(44.5mm)
1-3/4"
(44.5mm)
4-1/4"
(108mm)
1"
(25.4mm)
86-3/4"
(2203.5mm)
C
A
B
42"
(1067mm)
DPN000701 Rev0
DISCONTINUED
PRODUC T