Installation manual

Air Cooled Models
31
3.4 Fan Speed Control Systems
Fan Speed Control provides an infinite number of speed variations on specially designed permanent
split-capacitor motors. The control module varies the air quantity passing over the condenser coil by
monitoring refrigerant pressure.
3.4.1 Materials Supplied
Built-in, pre-wired condenser control box
Air cooled condenser
Piping access cover to be reinstalled when piping is complete
Bolts – four per leg (3/8"x5/8")
Terminal block for two-wire, 24V interlock connection between unit and condenser
Condenser legs – four with 1-fan, 2-fan and 3-fan models; six with 4-fan models
3.4.2 Dehydration
1. Open all disconnect switches.
2. Pull all fuses except transformer fuses. On units supplied with circuit breakers, open all breakers
except for the transformer.
3. Turn disconnects ON and jumper Fan Safety Switch between Common and Normal Open.
4. To energize the solenoid valves, use manual override jumpers (on SM). On AM and AG, set the
temperature set point (see operation manual) to 60°F (15°C) to ensure that solenoid valves are
open during the dehydration procedure.
5. Connect refrigeration gauges to the suction and discharge service valves of compressors 1 & 2.
6. Open all service valves.
Connect refrigerant gauges to both the suction and discharge service valves of the compressors. Start-
ing with circuit #1, open the service valves and place 150 PSIG (1034 kPa) of dry nitrogen with a
tracer of Freon. Check system for leaks.
With pressure in circuit: #1, open the service valves in circuit #2. If pressure increases in circuit #2,
the system is cross-circuited and must be rechecked for proper piping. If there is no pressure increase,
repeat leak check procedure for circuit #2.
After completion of leak testing, release the test pressure and pull a vacuum on the system. Leave
this vacuum for approximately 4 hours. Check the pressure to make sure that it has not increased. If
there is no change in pressure, pull another vacuum to 250 microns or less. Recheck the pressure
after two hours. After completion of this step, fill the circuits with Freon vapor until suction and dis-
charge pressures have equalized.
3.4.3 Charging
Remove the reheat and humidifier fuses (or open circuit breakers). Remove all shipping blocks from
the compressors and insure that all operational components are clear of debris. Turn the disconnect
on and check the evaporator fan for proper rotation. Set the temperature set point (see Operation
Manual) to 60°F (15°C) to ensure that solenoid valves are open during the charging procedure. Con-
nect the refrigerant gauge charging hose to the drum of refrigerant and purge the hoses of non-con-
densables. Add refrigerant vapor to the suction side of the compressor to eliminate short-cycling. The
low-pressure switch may be manually energized to expedite charging.
As head pressure builds the condenser fan will start rotating. The fan will become fully energized
when sufficient head pressure is developed. Charge the unit until the liquid line sight glasses become
clear. Watch the sight glasses for a period of 10 minutes to insure that no bubbles reappear. At this
point, add additional refrigerant to the circuit so that 5-10°F (3-5°C) subcooling is obtained in each
liquid line.
DISCONTINUED
PRODUC T