Installation manual

Glycol Cooled/GLYCOOL™ Models
40
Figure 26 Downflow GLYCOOL
cooled (DE) piping connections
Table 30 Downflow GLYCOOL (DE) piping connection sizes, inches
GLYCOOL Models
60 Hz (50 Hz)
A
(OD CU)
B
(OD CU)
DE072G (DE072G)
1-5/8 1-5/8DE110G (DE111G)
DE116G (DE121G)
DE192G (DE192G)
2-1/8 2-1/8DE240G (DE240G)
DE363G (DE363G)
MONITORING
PANEL
NOTE: Install all piping
per local codes.
3/4" NPT Condensate Drain.
Field pitch a min. of
1/8" (3.2mm) per ft. (305mm).
Do not install an
external trap.
1/4" OD CU Humidifier Supply Line
Steam Gen./Infrared)
B
- Glycol Supply Line.
A - Glycol Return Line.
DPN000588_Rev0