Installation and Assembly
19
3.4 Install an Optional RPCBDM
in the Rack
The RPCBDM (Basic Display Module) can be mounted in the rack with either the included hardware
or with a cable tie through the slot on the back of the module (see Figure 17). Either method permits
moving the RPCBDM to a different place in the same rack or to another rack.
3.4.1 Mounting Hardware
Spring nut M5: 1
Spacer sleeve: 1
Special MPX screw: 1
Cable clip: 1
Tools Required
Flat-blade screwdriver
3.4.2 RPCBDM Installation on Knurr
®
Miracel
Frame
1. Determine the mounting location in the rack.
2. Insert a spring nut into a T-slot on the frame member where the RPCBDM will be installed (refer
to Figure 9).
3. Insert the Liebert
®
MPX
screw into the spacer sleeve.
4. Insert the Liebert MPX screw into the spring nut and tighten securely with the screwdriver.
5. Hang the RPCBDM on the Liebert MPX screw with the hooded mounting slot on the back of the
RPCBDM (see Figure 17).
6. Connect the RPCBDM to the Liebert RPC
with an Ethernet cable.
Be certain to connect the cable to the correct port on the Liebert RPC (see Figure 18).
Figure 17 RPCBDM installation in rack
Cable tie fits in small
slot on RPCBDM,
loops around cabinet
member
Head of the Liebert MPX Screw
in frame fits into hooded slot
on back of RPCBDM