Datasheet

Specifications
28
7.3 MPX
BRM
—Model Number Configuration
Prefix: MPXBRM-
Region: N=North America; E=European
Type: B=Branch Monitoring; R=Receptacle Management; E=Elementary (No Monitoring)
Size and OL Protection:
A=Small (220mm), B=Standard (266mm), C=Standard w/ Tamper-Proof Screws
Output Power:
Voltage/CB Rating: A=120V,20A; B=208V,20A; C=230V,20A; D=208-240V,20A; E=100V,20A;
F=240V,20A
Number of Receptacles: 2 to 7
Receptacle Type: A=5-20R; F to L=Reserved; N=IEC-C13 Sheet F; O=IEC-C19 Sheet J;
P=CEE-7 Type F (Schuko); U=GST18
Phase Configuration: 1N=L1-N; 2N=L2-N; 3N=L3-N; 12=L1-L2; 23=L2-L3; 31=L3-L1
Table 3 MPX BRM (Branch Receptacle Module) specifications
Model # Type
No. of
Outlets
Receptacle Ratings
OCB, A
Voltage
Configuration
Length,
mm Region
Weight
lb. (kg)Ampere, A Voltage, V
RECEPTACLE MANAGEMENT MODULES
North American Applications
MPXBRM-NRBA6A1N NEMA 5-20R 6 16 120 20 L1-N 266 NA 2.3 (1.03)
MPXBRM-NRBA6A2N NEMA 5-20R 6 16 120 20 L2-N 266 NA 2.3 (1.03)
MPXBRM-NRBA6A3N NEMA 5-20R 6 16 120 20 L3-N 266 NA 2.3 (1.03)
MPXBRM-NRBD4O12 IEC C19 Sheet J 4 16 208-240 20 L1-2 266 NA 2.3 (1.03)
MPXBRM-NRBD4O23 IEC C19 Sheet J 4 16 208-240 20 L2-3 266 NA 2.3 (1.03)
MPXBRM-NRBD4O31 IEC C19 Sheet J 4 16 208-240 20 L3-1 266 NA 2.3 (1.03)
MPXBRM-NRBD6N12 IEC C13 Sheet F 6 12 208-240 20 L1-2 266 NA 2.3 (1.03)
MPXBRM-NRBD6N23 IEC C13 Sheet F 6 12 208-240 20 L2-3 266 NA 2.3 (1.03)
MPXBRM-NRBD6N31 IEC C13 Sheet F 6 12 208-240 20 L3-1 266 NA 2.3 (1.03)
MPXBRM-NRBF4O12 IEC C19 Sheet J 4 16 240 20 L1-N 266 NA 2.3 (1.03)
MPXBRM-NRBF4O23 IEC C19 Sheet J 4 16 240 20 L2-N 266 NA 2.3 (1.03)
MPXBRM-NRBF4O31 IEC C19 Sheet J 4 16 240 20 L3-N 266 NA 2.3 (1.03)
MPXBRM-NRBF6N12 IEC C13 Sheet F 6 12 240 20 L1-N 266 NA 2.3 (1.03)
MPXBRM-NRBF6N23 IEC C13 Sheet F 6 12 240 20 L2-N 266 NA 2.3 (1.03)
MPXBRM-NRBF6N31 IEC C13 Sheet F 6 12 240 20 L3-N 266 NA 2.3 (1.03)
RECEPTACLE MANAGEMENT MODULES
European Applications
MPXBRM-ERBC3P1N Schuko CEE 7/4 3 16 230 20 L1-N 266 EU 2.3 (1.03)
MPXBRM-ERBC3P2N Schuko CEE 7/4 3 16 230 20 L2-N 266 EU 2.3 (1.03)
MPXBRM-ERBC3P3N Schuko CEE 7/4 3 16 230 20 L3-N 266 EU 2.3 (1.03)
MPXBRM-ERBC4O1N IEC C19 Sheet J 4 16 230 20 L1-N 266 EU 2.3 (1.03)
MPXBRM-ERBC4O2N IEC C19 Sheet J 4 16 230 20 L2-N 266 EU 2.3 (1.03)
MPXBRM-ERBC4O3N IEC C19 Sheet J 4 16 230 20 L3-N 266 EU 2.3 (1.03)
MPXBRM-ERBC6N1N IEC C13 Sheet F 6 10 230 20 L1-N 266 EU 2.3 (1.03)
MPXBRM-ERBC6N2N IEC C13 Sheet F 6 10 230 20 L2-N 266 EU 2.3 (1.03)
MPXBRM-ERBC6N3N IEC C13 Sheet F 6 10 230 20 L3-N 266 EU 2.3 (1.03)