Datasheet

Specifications
31
7.5 Agency Approvals
120V and 240V Single-Phase and 120/208-240V Three-Phase North American Units
UL60950-1: Information Technology Equipment - Safety, Part 1 General Requirements
CSA C22.2 No. 60950-1: Information Technology Equipment - Safety, Part 1 General
Requirements
FCC, Title 47, Part 15 Subpart B for Class B operation as defined by ANSI Standard C63.4.
ISTA Procedure 1A and 2A
RoHS Compliant
230V Single-Phase and 400V Three-Phase European Units
CE Markings GS mark (safety tested) according to DIN EN 60950-1 (VBE 0805-1) 2006/95/EC
and EMC Directive (EMD) 2004/108/EC according to the Low-Voltage Directive (LVD)
CE Compliant according to:
Low-Voltage Directive 2006/95/EC
Electromagnetic - Compatibility Directive 2004/108/EC (EMD)
RoHS Directive 2002/95/EC
WEE Directive 2002/96/EC
ISTA Procedure 1 A and 2A
ROHS and WEEE Compliant, Basic Test for Purchased Products according to International Safe
Transit Association
Table 5 Electrical and environmental specifications
Power Consumption, W
22 maximum per fully configured 42U model (RPC, BDM, PEM, 6xBRM-R)
3 per RPC; 0.4 per module + 0.4 per open control (energized condition)
Maximum Ratings 240/415V 50/60Hz 63A
Insulation Class I, Basic Earthed SELV
Electric Strength, VDC 2200
Overcurrent Protection UL489 Overcurrent Circuit Breaker per Branch, 20A, 5000A A.I.C
Operating Temperature, °C (°F) 5-55 (41-131)
Humidity, % 10-95, non-condensing
Altitude, m (ft.) 2000 (6560)
Table 6 Metering performance
Accuracy, %
Volts, V ±1
Current, A (per %rated value)
±2 from 1% to <10%
±1 from 10% to 125%
Measurement, Resolution Power Entry Module (PEM)
Branch Receptacle Module (BRM
)
Branch Receptacle
Phase Voltage, 0.1V
Line Voltage, 0.1V ——
Line Current, 0.01A √√
Neutral Current, 0.01A
(3-phase only)
——
Total Real Power, 0.1W ——
Total Real Energy, 0.1kW-hr ——
Real Power, 0.1W √√
Apparent Power, 0.1VA √√
Real Energy, 0.1kW-hr √√
Power Factor, 0.01 √√
Crest Factor, 0.01
Frequency, 0.1Hz ——