User manual

Installation
9 Emerson
®
RPC2
Figure 3 Rack PDU Array layout examples
Table 4 IP addresses in a Rack PDU Array
IP Address Rack PDU 1 Rack PDU 2 Rack PDU 3 Rack PDU 4
Link Port 192.168.1.10 192.168.1.6 192.168.1.2 192.168.1.14
Network Port User Determined 192.168.1.9 192.168.1.5 192.168.1.1
Subnet Mask 255.255.255.252 255.255.255.252 255.255.255.252 255.255.255.252
Table 5 Laptop IP settings for RPC2 communications module addresses
IP Address Rack PDU 1 Rack PDU 2 Rack PDU 3 Rack PDU 4
Laptop Computer 192.168.1.9 192.168.1.5 192.168.1.1 192.168.1.13
Link Port 192.168.1.10 192.168.1.6 192.168.1.2 192.168.1.14
Subnet Mask 255.255.255.252 255.255.255.252 255.255.255.252 255.255.255.252
RPC2 communications
module in MASTER PDU
RPC2 communications
module in Sibling PDU
TO
NETWORK
RPC2 communications
module in Sibling PDU
RPC2 communications
module in Sibling PDU
RPC2 communications
module in MASTER PDU
RPC2 communications
module in Sibling PDU
TO
NETWORK
RPC2 communications
module in Sibling PDU
RPC2 communications
module in Sibling PDU
Ethernet cable between
Link Port and Network Port
Ethernet cable
between Link
Port and
Network Port
Ethernet cable
between Link
Port and
Network Port
Ethernet cable
between Link
Port and
Network Port
Ethernet cable
between Link
Port and
Network Port
Ethernet cable
between Link
Port and
Network Port