EMPIRE Comfort Systems INSTALLATION INSTRUCTIONS AND OWNER’S MANUAL Direct Vent Zero Clearance Gas Fireplace Heater Direct vent Gas Fireplace heater Model series millivolt dvcd32fp30(n,p)-1 dvcd36fp30(n,p)-1 dvcd42fp30(n,p)-1 GAS-FIRED DIRECT IGNITION dvcd32fp50n-1 dvcd36fp50n-1 dvcd42fp50n-1 UL FILE NO. MH30033 WARNING HOT GLASS WILL CAUSE BURNS. DO NOT TOUCH GLASS UNTIL COOLED. NEVER ALLOW CHILDREN TO TOUCH GLASS. Installer: Leave this manual with the appliance.
TABLE OF CONTENTS Section Page Important Safety Information .......................................................................................................................... 3 Safety Information for Users of LP Gas . ........................................................................................................ 4 Requirements for Massachusetts ................................................................................................................... 5 Introduction . .............
IMPORTANT SAFETY INFORMATION Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly. DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED • If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance. • Clothing or other flammable material should not be placed on or near the appliance.
SAFETY INFORMATION FOR USERS OF LP GAS Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point by point with the members of your household. Someday when there may not be a minute to lose, everyone’s safety will depend on knowing exactly what to do.
REQUIREMENTS FOR MASSACHUSETTS For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 3. SIGNAGE.
INTRODUCTION Instructions to Installer 1. Installer must leave instruction manual with owner after installation. 2. Installer must have owner fill out and mail warranty card supplied with the fireplace. 3. Installer should show owner how to start and operate the fireplace. This direct vent gas fireplace heater is designed to operate with all combustion air being siphoned from the outside of the building and all exhaust gases expelled to the outside of the building.
SPECIFICATIONS Input BTU/Hr Maximum BTU/Hr Minimum (millivolt only) KWH (Maximum) (Minimum) NAT. Orifice Air Shutter Opening LP Orifice Air Shutter Opening Height without standoff Width Depth Gas Inlet Shutoff Valve (Pipe) DVCD32 18,000 14,000 5.3 4.1 DVCD36 20,000 14,000 5.9 4.1 DVCD42 25,000 18,000 7.3 5.3 #46 (.081") P-254 1/16" (1.6 mm) 2.10 mm P-288 1/16" (1.6 mm) #42 (.0935") P-286 3/16"(4.8 mm) #56 (.0465") P-287 1/4" (6.3 mm) 32 3/4" (832 mm) 34" (864 mm) 16 3/8" (416 mm) 1/2 NPT #55 (.
FIREPLACE DIMENSIONS LEFT SIDE VIEW RIGHTSIDE SIDE VIEW RIGHT VIEW FRONT VIEW GAS LINE ACCESS ELECTRICAL ACCESS J H Dim DVCD32 DVCD36 DVCD42 A 34" 864 mm 37" 940 mm 43" 1092 mm B 31" 787 mm 34" 864 mm 40" 1016 mm C 23 1/16" 585 mm 23 1/16" 585 mm 25 1/16" 636 mm D 35 5/8" 905 mm 35 5/8" 905 mm 37 5/8" 956 mm E 32 3/4" 832 mm 32 3/4" 832 mm 34 3/4" 883 mm F 16 3/8" 416 mm 16 3/8" 416 mm 16 3/8 416 mm G 24 1/2" 622 mm 24 1/2" 622 mm 26 1/2" 673 mm H 7 1/8" 181 mm 7 1/8"
CLEARANCES Mantel Chart (Figure 4) Clearance to Combustibles Back 0" (0 mm) Side 0" (0 mm) Floor 0" (0 mm) Top Stand-off 0" (0 mm) Top Framing Edge 3" (76 mm) 12” (305mm) 10” (254mm) MANTEL SEE MANTLE CHART FOR MAXIMUM MANTLE DEPTH 15” (381mm) 2" x 4" HEADER 6” 4 ½” STAND OFF 3" (76 mm) HEIGHT ABOVE TOP OF FIREPLACE SEE MANTLE CHART FOR MINIMUM HEIGHT OF MANTLE ABOVE UNIT COMBUSTIBLE TRIM AND MANTELS ALLOWED IN SHADED AREA 8” 3 3/4” 13 3/4” 3” 2 1/4” 11” 1 ½” 9” 8” FINISHED WALL (COMBUSTIBL
LOCATING FIREPLACE CABINET INSTALLATION CORNER INSTALLATION ISLAND INSTALLATION ANGLED CORNER INSTALLATION FLUSH WALL INSTALLATION ROOM DIVIDER INSTALLATION Note: Island (C) and Room Divider (D) installation is possible as long as the horizontal portion of the vent system (H) does not exceed 20 feet with a minimum vertical run of 8 feet. See details in Venting Section.
GAS SUPPLY The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code. Recommended Gas Pipe Diameter Pipe Length Schedule 40 Pipe Inside Diameter Tubing, Type L Outside Diameter Nat. L.P. Nat. L.P. 0-10 feet 0-3 meters 1/2” 12.7 mm 3/8” 9.5 mm 1/2” 12.7 mm 3/8” 9.5 mm 10-40 feet 4-12 meters 1/2” 12.7 mm 1/2” 12.7 mm 5/8” 15.9 mm 1/2” 12.
REAR VENT CONVERSION VERTICAL VENTING HORIZONTAL VENTING Note: Discard insulation & retainer when venting off top of fireplace. INLET VENT COVER PLATE Note : Discard insulation & retainer when using vertical venting off Note : It is recommended that the flue cover plate tab be pulled outward prior to removal. FLUE COVER PLATE INLET VENT COLLAR INSULATION RETAINER FLUE OUTLET COLLAR This will ensure that the plate is not accidentally dropped inside the rear air chamber.
INSTALLATION Framing and Finishing 1. Choose unit location. 2. Frame in fireplace with a header across the top. It is important to allow for finished face when setting the depth of the frame. 3. Attach fireplace to frame using adjustable frame. Preset depth to suit facing material (adjustable to 1/2", 5/8" or 3/4" depths). 4. Use (8) 1/2" hex-head screws supplied in hardware package, to screw through slotted holes in drywall strip and then screw into pre-drilled holes on fireplace side.
INSTALLATION (continued) Flush Mount Mantel Installation (Figure 12) The fireplace must extend 3/4" beyond finished wall surface when using a flush mount mantel. Refer to Figure 12 to locate nailing flanges on fireplace sides. Mark and drill two (2) 1/8" holes into fireplace side to mount each nailing flange. Use eight (8) 1/2" hexhead screws supplied in hardware package to attach nailing flanges to fireplace sides. Note: For finishing to top of fireplace, refer to Figure 14.
INSTALLATION (continued) Flush Wall Installation FINISHED WALL 3” (76.2mm) OF NON-COMBUSTIBLE MATERIAL FRONT TRIM OR NON-COMBUSTIBLE MATERIAL (INSTALLATION IS OPTIONAL) JOINT BETWEEN FINISHED WALL AND UNIT SEALED WITH 300° F, 149° C SEALANT MATERIAL (SEALANT IS OPTIONAL) Attention: Cold climate installation recommendation: When installing this unit against a non-insulated exterior wall, it is recommended that the outer walls be insulated to conform to applicable insulation codes.
INSTALLATION (continued) Horizontal only, straight out the back " A" PIPE LENGTH VENT CAP WALL FIRESTOP/ THIMBLE "A" "B" Models 6" 5 1/8" to 6 1/2" (130 mm to 165 mm) DVCD 32,36,42,48 9" 8 1/8" to 9 1/2" (206 mm to 241 mm) DVCD 32,36,42 12" 11 1/8" to 12 1/2" (283 mm to 317 mm) DVCD 32,36,42 Figure 17 vertical, 90° elbow to horizontal out the wall WALL FIRESTOP/ THIMBLE "A" "B" "C" 6" 11 1/4" to 12 3/4" (286 mm to 324 mm) 4 3/4" to 6 1/4" (121 mm to 159 mm) 9" 14 1/4" to 15 3/4" (362
INSTALLATION (continued) Corner installation vertical, 90° elbow to horizontal out the wall WALL FIRESTOP/ THIMBLE VENT CAP Dim.
VENTING FIREPLACE - TOP To Use the Vent Graph (Figure 21) 1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent Graph, locate the point it intersects with the slanted graph line. 2. From the point of this intersection, draw a vertical line to the bottom of the graph. 3. Select the indicated dimension, and position the unit in accordance with same. Venting Graph (Dimensions in Feet) EXAMPLE B: If the vertical dimension from the floor of the unit is 6.
VENTING FIREPLACE - TOP (continued) Below Grade Installation When it is not possible to meet the required vent terminal clearances of 12" (305 mm) above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178 mm) below grade level. The 7" (178 mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall. Ensure the sidewall venting clearances are observed.
VENTING FIREPLACE - TOP (continued) D C B V H Cutting the Hole (Figures 25) After the fireplace has been positioned in its permanent location, the hole through the exterior wall of the house can be cut. This hole must be 10" (254mm) high x 10" (254mm) wide with its center line determined by the amount of vertical rise and horizontal run of the termination.
EXAMPLES - TOP VENT RUN 24” 24” MINIMUM CLEARANCE TO COMBUSTIBLES Figure 29 Figure 28 Figure 30 28365-2-0811 Page 21
VENTING FIREPLACE - REAR EXAMPLE A: If the vertical dimension from the floor of the unit is 12 feet, 4 inches the horizontal run to the outer wall flange must not exceed 12 feet, 3 inches. EXAMPLE B: If the vertical dimension from the floor of the unit is 6 feet, 9 inches, the horizontal run to the outer wall flange must not exceed 6 feet, 6 inches. Special Note: For each 45 degree elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (457 mm).
EXAMPLES - REAR VENT RUN Model Maximum Pipe Length H1 DVCD32 24" DVCD36 24" DVCD42 24" DVCD48 6" Figure 34 Figure 32 Model Figure 33 28365-2-0811 Maximum Pipe Length H1 DVCD32 24" DVCD36 24" DVCD42 24" DVCD48 N/A Figure 35 Page 23
TERMINATION CLEARANCES Termination clearance for buildings with combustible and noncombustible exteriors. Figure 36 Vertical Sidewall Installations Important! Minimum clearance between vent pipes and combustible materials is three (3") (76 mm) on top, and (1") (25 mm) on bottom and sides. Important! When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must extend outward so that the horizontal vent terminal is located flush to, or beyond the outcrop siding.
VENT CLEARANCES Figure 37 A = *Clearance above grade, veranda, porch, deck or balcony [*12 inches (305 mm) minimum] B = clearance to window or door that may be opened [*12 inches (305 mm) minimum for appliances < 100,000 BTU/ Hr (30 kW) C = clearance to permanently closed window [minimum 12 inches (305 mm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (610 mm) from the center of the term
VENT SYSTEM IDENTIFICATION Installing Vent Components (Figure 38) Begin the vent system installation by installing the first Simpson Duravent component, 90° elbow to the starting collars or straight pipe on the top of the appliance, then the straight pipe length and then horizontal or vertical termination kit. NOTE: All outer connection joints must be sealed with aluminum tape, screws or silicone sealant rated above 300°F/149°C. The inner flue joints do not require any sealant.
FRAMING AND FINISHING Installing Support Brackets (Figure 39) A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports should be placed around the pipe and nailed in place to framing members. There MUST BE a 3 inch clearance to combustibles above 6 5/8 inch diameter pipe and elbows and 1 inch clearance on both sides and bottom of 6 5/8 inch pipe to combustibles on all horizontal pipe sections and elbows.
FRAMING AND FINISHING (continued) Vertical Firestops (Figures 41, 42 and 43) Vertical runs of this system which pass through ceilings require the use of ONE (1) ceiling firestop at the hole in each ceiling through which the vent passes. Position a plumb bob directly over the center of the vertical vent component and mark the ceiling to establish the center point of the vent. Drill a hole or drive a nail through this center point and check the floor above for any obstructions such as wiring or plumbing runs.
HORIZONTAL TERMINATION NOTE: Termination cap should pass through the wall firestop from the exterior of the building. Adjust the termination cap to its final exterior position on the building. Warning: Termination cap must be positioned so that arrow is pointing up. Attach the termination cap with the four wood screws provided. Before attachment of the termination, run a bead of silicone sealant rated above 250°F on its outside edge too, so as to make a seal to the exterior wall.
DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS CAUTION: Sharp edges, use protective gloves when installing. Tools Needed for Installation: Sheet metal snips 5/16” nut driver Phillips head screwdriver - #2 High temperature sealant or furnace cement rated for continuous use at 1,000ºF minimum Measuring tape NOTE: SPACING FLANGE INSTALLED TO TOPSIDE 11” Parts Verification See parts list on page 32 to verify components included in this vent kit prior to installation.
DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS (continued) VINYL SIDING KIT DV822 OUTSIDE MOUNTING PLATE MEASURE OUTSIDE WALL Figure 49 EXT. WALL SURFACE OR VINYL SIDING KIT FLUE PIPE 7. Remove outside mounting plate with tube attached from wall. Mark and cut the extra length of the 6 5/8” (168 mm) diameter tube from the opposite end. Do not crimp or enlarge tube. 8. Attach the 4” (102 mm) diameter flue outlet tube onto the rigid venting system or directly to fireplace.
DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS (continued) Follow correct option according to venting method. 6 Connecting Directly to Fireplace If the air inlet and flue outlet tubes are to be connected directly to the unit (no rigid venting system is being used), then the gasket provided must be used to seal the 4” (102 mm) flue outlet tube. Peel the paper off the self-adhesive gasket and then wrap it around the end of the tube (if tube was cut, it is recommended to use cut end) as shown in Figure 51.
DVVK-4F FLEX VENT INSTRUCTIONS INSTALLATION 1. Unpack vent components and check that all items are included. 2. Check to see that the vent spacer springs are located around the flue vent at 8" and 12" intervals along its length. See Figure A. If not, stretch the spacer springs to about 15" long and wrap them around the flue, then interlock the ends of each spring about 2". See Figure B. Maintain equal distance between spring spacers. 3. Remove the 6-⅝" diameter Vent collar from the fireplace.
VERTICAL TERMINATION Locate and mark the center point of the vent pipe using a nail on the underside of the roof. Drive the nail through the center point. Mark the outline of the roof hole around this center point. NOTE: Size of the roof hole dimensions depend on the pitch of the roof. There must be a 1 inch clearance (25 mm) to the vertical pipe sections. This clearance is to all combustible material. Cover the opening of the vent pipe and cut and frame the roof hole.
VERTICAL TERMINATION (continued) Installation of Vertical Inlet Baffle The vertical inlet baffle is to be used only in a completely vertical vent installation. The vertical inlet baffle can be used when the vertical vent rise is between 10 feet and 40 feet. To maintain the yellow flame in the main burner, purchase Vertical Inlet baffle, DVF-139 from your Empire Comfort Systems, Inc. distributor or dealer for Simpson Duravent only.
LOG PLACEMENT - 32” & 36” FIREPLACES Before you begin: if you are installing logs into the DVCD32 or DVCD36 models then this fireplace is supplied with a set of six ceramic fiber logs. Do not handle these logs with your bare hands! Always wear gloves to prevent skin irritation from ceramic fibers. After handling logs, wash your hands gently with soap and water to remove any traces of fibers. The positioning of the logs is critical to the safe and clean operation of this fireplace.
LOG PLACEMENT - 42” FIREPLACES Before you begin: If you are installing logs into the DVCD42 model then this fireplace is supplied with a set of seven ceramic fiber logs. Do not handle these logs with your bare hands. Always wear gloves to prevent skin irritation from ceramic fibers. After handling logs, wash your hands gently with soap and water to remove any traces of fiber. The positioning of logs is critical to safe and clean operation of this fireplace.
OPERATING INSTRUCTIONS 750 Millivolt System The standing pilot (750 millivolt system) is a continuous burning pilot. The pilot remains ON even when the main burner is OFF. The OWNER should carefully read and follow these operating instructions at all times. Lower the door assembly to view the gas controls for the fireplace. When you ignite the pilot, the thermopile produces millivolts (electrical current) which energizes the magnet in the gas valve.
OPERATING INSTRUCTIONS (continued) standing pilot Operating Instructions Remote/Off/On Switch The fireplace is equipped with a Remote/OFF/ON switch. A wire harness is attached to the Remote/OFF/ON switch. The red, black and green (wires) female push-ons attach to the Remote/ OFF/ON switch. At the opposite end of the wire harness, the black and green (wires) female push-ons attach to the gas valve.
STANDING PILOT WIRING DIAGRAM (OPTIONAL) THERMOSTAT (OPTIONAL) WALL SWITCH Figure 62 Page 40 28365-2-0811
STANDING PILOT LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. Before lighting smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
STANDING PILOT TROUBLESHOOTING With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken. 1. Spark ignitor will not light pilot after repeated triggering of piezo ignitor button. a.
DIRECT IGNITION WIRING DIAGRAM (OPTIONAL) WALL SWITCH OR THERMOSTAT INTERRUPTEUR MURAL (FACULTATIVE) MAIN VALVE RETURN 1 GROUND 2 120V AC HOT 6 120V AC RETURN 4 13 120 VAC RTN 12 120 VAC LINE BLACK NOIR BLACK NOIR WHITE BLANC GREEN VERT JUNCTION BOX JONCTION BOÎTE GAS VALVE VALVE DE GAZ CONTROL MODULE AUTORITÉ MODULE MAIN VALVE HOT 8 (OPTIONAL) REMOTE CONTROL RECEIVER 120V (FACULATIVE) CONTROLE E DISTANCE DU RECEPTEUR SPARK IGNITOR ÉTINCELLE ALLUMER RED ROUGE LED LIGHT LED LUMIÈRE LED CODES
DIRECT IGNITION LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE. A. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
INITIAL START UP GAS LINE PURGE NOTE: UNIT MUST BE PROPERLY GROUNDED FOR ELECTRONIC IGNITION TO FUNCTION. On initial installation, or after extended periods where the fireplace has not been used, gas lines may require purging. The installer or qualified service person may use the following purge procedures to prevent the delays that would be caused by waiting for the lockout periods between tries for ignition. PURGE PROCEDURE 1. Remove glass door and place away from the fireplace. 2.
DIRECT IGNITION PROPANE/LP GAS CONVERSION The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in accordance with the requirements of the CSA B149.2 installation code (Canada) and with the requirements of the National Fuel Gas Code Z223.1/NFPA 54 (United States).
DIRECT IGNITION PROPANE/LP GAS CONVERSION Maxitrol Valve Conversion “A” Model AIR SHUTTER SETTINGS BURNER ORIFICE Opening "A" Propane/LP Orifice DVCD32 1/4" (6.4 mm) #56 DVCD36 1/4" (6.4 mm) #55 DVCD42 5/16" (7.9 mm) 1.
MAINTENANCE AND SERVICE Please Note It is normal for appliances fabricated of steel to give off some expansion and/or contraction noise during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine. It is not unusual for your gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process. Please ensure that your room is well ventilated - open all windows.
MASTER PARTS DISTRIBUTOR LIST To Order Parts Under Warranty, please contact your local Empire dealer. See the dealer locator at www.empirecomfort. com. To provide warranty service, your dealer will need your name and address, purchase date and serial number, and the nature of the problem with the unit. To Order Parts After the Warranty Period, please contact your dealer or one of the Master Parts Distributors listed below. This list changes from time to time.
PARTS LIST INDEX NO.
PARTS LIST INDEX NO. PART NUMBER DESCRIPTION DVCD32 DVCD36 DVCD42 31 R7624 R7624 R7624 AIR SHUTTER 32 P254 P288 P286 ORIFICE (NAT) 32 P287 P182 P208 ORIFICE (LP) 33 R7575 R7575 R7575 34 P212 P212 P212 ORIFICE FITTING 35 23550 23550 23551 TUBING ASSEMBLY 36 R2423 R2423 R2423 MALE CONNECTOR 37a R7577 R7577 R7577 VALVE, SIT GAS - NAT 37a R7578 R7578 R7578 VALVE, SIT GAS - L.P.
PARTS VIEW 1 2 19 3 4 7 8 5 11 9 10 11 12 6 16 52 19 13 17 13 13 18 51 13 14 15 28 31 32 33 29 45 41b 39 30 39 41a 50 46b 48 30 37a 35 38 50 40a 34 37b 36 29 31 32 33 40b 44 34 35 28 52 38 36 52 43 47 46a 42 MILLIVOLT BURNER ASSEMBLY 49 20 DIRECT IGNITION BURNER ASSEMBLY 20 26 21 25 25 27 24 22 27 21 22 23 7 PIECE LOG ASSEMBLY Page 52 23 8 PIECE LOG ASSEMBLY 28365-2-0811
FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION Attention: Install blower assembly before connecting gas inlet supply line Note: Junction box on right side of fireplace must be pre-wired at time of fireplace installation for use with blower assembly. It is recommended that an ON/OFF wall switch be installed that will activate the power supply to the furnace by a qualified electrician. 1. 2. 3. 4. If installed, turn OFF gas supply to fireplace. If applicable, turn OFF electric supply to fireplace.
FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION 1 FBB4 BLOWER ASSEMBLY COMPLETE 2 R7649 FAN CONTROL 3 R4192 SPEED CONTROL KNOB 4 R4186 SPEED CONTROL JUNCTION BOX 110 VOLT AC FAN BLACK FAN SWITCH WHITE SPEED CONTROL Page 54 GROUND 28365-2-0811
JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS STANDARD MILLIVOLT VALVE MODELS CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION, MAKE SURE THAT MAIN POWER SUPPLY IS DISCONNECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE ANSI/NFPA 70 (LATEST EDITION).
OPTIONAL BRICK LINER INSTALLATION INSTRUCTIONS 1. Using gloves, unpack liner components and check for damaged or missing components. 2. Lower bottom louver and remove upper louver on fireplace. 3. Remove glass frame assembly from fireplace. 4. Remove rear logs from burner assembly. 5. Place brick panel (rear) against rear wall in fireplace. Note: The top edge will have a half-moon cutout relief to match up with the rear flue vent hole. 6.
ACCESSORIES The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond what your dealer can furnish, contact Empire Comfort Systems Inc., Nine Eighteen Freeburg Ave., Belleville, Illinois 62220-2623. Accessory Description Model Number Fan Kit This fan kit is designed to provide forced air flow.
APPLIANCE SERVICE HISTORY Date Dealer Name Page 58 Service Technician Name Service Performed/Notes 28365-2-0811
APPLIANCE SERVICE HISTORY Date Dealer Name 28365-2-0811 Service Technician Name Service Performed/Notes Page 59
EMPIRE Comfort Systems Empire Comfort Systems Inc. 918 Freeburg Ave. Belleville, IL 62220 If you have a general question about our products, please e-mail us at info@empirecomfort.com. If you have a service or repair question, please contact your dealer. www.empirecomfort.