Owner`s manual

28365-2-0811Page 18
To Use the Vent Graph (Figure 21)
1. Determine the height of the center of the horizontal vent pipe.
Using this dimension on the Sidewall Vent Graph, locate the
point it intersects with the slanted graph line.
2. From the point of this intersection, draw a vertical line to the
bottom of the graph.
3. Select the indicated dimension, and position the unit in
accordance with same.
EXAMPLE A:
If the vertical dimension from the oor of the unit is 35 feet, the
horizontal run to the outer wall ange must not exceed 6.5 feet.
EXAMPLE B:
If the vertical dimension from the oor of the unit is 6.5 feet, the
horizontal run to the outer wall ange must not exceed 14.5
feet.
SPECIAL NOTE: For each 45 degree elbow installed in the
horizontal run, the length of the horizontal run MUST be reduced
by 18" (457 mm). This does not apply if the 45 degree elbows
are installed on the vertical part of the vent system. Reduce 3'
for every 90° elbow.
Example: According to the chart the maximum horizontal vent
length is 20' and if two 45 degree elbows are required in the
horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per side
wall installation is two (2). These elbows can be installed in either
the vertical or horizontal run.
Note: On vertical venting the rst elbow does not get counted.
Acceptable vertical and horizontal vent run.
(40' maximum vertical and 20' maximum horizontal)
Unacceptable vertical and horizontal vent run.
Figure 21
Venting Graph (Dimensions in Feet)
VERTICAL DIMENSION FROM THE BOTTOM OF THE UNIT
TO THE CENTER OF THE FLUE OUTLET
WITH VERTICAL OR HORIZONTAL TERMINATION CAPS
VENTING FIREPLACE - TOP