Procedure To Set Or View Charger Setting
Follow the procedure or sequence in Appendix A1 and A2 (see pages 36
to 39 of this manual) to set or view the charger setting.
GEL, AGM Or Flooded Battery Type:
Parameters below are required for setting:
Battery type (GEL, AGM, Flooded)
Maximum Current setting (see table below)
Absorption to oat mode current setting (see table below)
Charging stage (3-stage , 2-stage)
Battery temperature (low, normal, high temperature) or connect the
temp sensor to over-ride
The following table shows the maximum available charging current and
its related available Absorption to Float Mode current.
Model Charging Voltage Maximum Charging Current Termination Charging Current
EN31220 14.2V / 14.3V / 14.4V
* 20A 2A / *4A / 6A
15A 1.5A / 3A / 5A
10A 1A / 2A / 3A
5A 0.5A / 1A / 1.5A
EN31240 14.2V / 14.3V / 14.4V
* 40A * 4A / 6A / 8A
20A 2A / 4A / 6A
10A 1A / 2A / 3A
5A 0.5A / 1A / 1.5A
EN31260 14.2V / 14.3V / 14.4V
* 60A * 6A / 9A / 12A
40A 4A / 6A / 8A
20A 2A / 4A / 6A
5A 0.5A / 1A / 1.5A
EN32430 28.4V / 28.6V / 28.8V
* 30A * 3A / 4.5A / 6A
20A 2A / 4A / 6A
10A 1A / 2A / 3A
5A 0.5A / 1A / 1.5A
Note: * Recommended setting (Factory Default Setting)
Page 25ww w.enerdrive.com.au