User Manual

Recommended Fuse Protection
From Alternator Battery
70amp Fuse or Circuit Breaker no greater than 20cm from source
battery.
PLEASE NOTE: Automatic re-settable circuit breakers are
NOT recommended.
From Solar Panels
Fusing recommended no greater than 20cm from input to DC2DC+
Charger. Typically 15amps per solar panel (consult your panel
specications for further details).
Primary Battery
Connection
60amp Fuse or Circuit Breaker.
Standard Temperature Sensor Connection
To install the temperature sensor, simply connect the RJ12 plug from the sensor to the
RJ12 Temperature Sensor Port located next to the Remote Port.
On the temperature sensor end, simply connect the ring terminals to the negative terminal
of the main house battery bank.
PLEASE NOTE: For lithium installations, the standard supplied temperature sensor is not
required to be installed for these applications.
Enerdrive ePOWER DC2DC+ Battery Charger Owners Manual (Rev. 1.00)Page 18