Unpacking the DC Power Supply
Matrix X Router DC Power Supply Installation Guide 1-9
Unpacking the DC Power Supply
TounpacktheDCpowersupply:
1. OpentheboxandremovethepackingmaterialprotectingtheDCpowersupply.
2. VerifythecontentsofthecartonaslistedinTable 14.
Warning: To reduce the risk of electric shock or energy hazards:
1. Connect to a reliably grounded 48V source.
2. The branch circuit over current protection must be rated at a maximum 50A for the
device.
3. Use only 10mm² or 6 AWG 75C solid copper wires on the device.
4. A readily accessible disconnect device that is suitably approved and rated shall be
incorporated in the field wiring.
5. To be installed in a restricted access area in accordance with the NEC or authority
having jurisdiction.
Advertencia: Para reducir el riesgo de choque electrico:
1. Conectar a una fuente aterrizada de 48V.
2. The branch circuit over current protection must be rated at a maximum 50A for the
device.
3. Utilizar unicamente cables de cobre solidos de tipo 75C 10mm² or 6 AWG en el
dispositivo.
4. A readily accessible disconnect device that is suitably approved and rated shall be
incorporated in the field wiring.
5. Ser instalado en una area de acceso restrictivo, de acuerdo con el NEC o con otra
autoridad.
Warnhinweis: Reduzieren sie das Risiko von Stromschlägen oder allgemeinen
elektrischen Gefahren:
1. Verbinden Sie das Gerät mit einer zuverlässig geerdeten 48 V Stromquelle.
2. Die maximale Absicherung des Stromkreises für dieses Gerät beträgt 50A.
3. Benutzen Sie zum Anschluß des Gerätes ausschließlich Kabel mit soliden Kupferadern
des Querschnitts 10mm² (6 AWG) 75C.
4. Das Stromnetz am Installationsort sollte mit einem frei zugänglichen Spannungs-
Unterbrecher (Not-Aus-Schalter) ausgestattet sein, der ausreichend ausgelegt ist und
den gängigen Bestimmungen entspricht.
5. Die Installation sollte in zugangskontrollierten Räumen erfolgen, entsprechend den
Vorschriften der NEC bzw. der örtlich zuständigen Behörden.