Fire Pit User Manual

27
Firebox Top
Flue Collar
Adapter
Undo four "
screws that
hold flue collar
elbow to unit.
Figure 40: Step 3 of Converting Top Vented into
Rear Vented.
Figure 41: Step 4 of Converting Top
Vented into Rear Vented.
INSTALLATION OF REAR VENTED APPLIANCE:
Siding
Exterior wall
Drywall
Vent pipe
Inside finished collar
Wall thimble
Minimum vent terminal 36"
(91.4cm) high snorkel kit.
Figure 42: Installation for Rear Vented;
30,000 Btu/hr.
2. Remove the four (4) ” screws that hold the ue collar elbow to the unit body (see Figure 40).
3. Carefully remove the elbow being sure not to damage the gasket that is glued to the ue collar elbow,
it seals the ue to the rebox.
4. Turn the elbow to the rear vent position and re-fasten with the screws removed in step 2 (see Figure
41).
Place the unit into position.
Attach a small section of pipe on the unit and mark exterior wall
where vent would pass through the wall.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain
clearances to combustibles. Frame hole as shown in Figure 26.
Install a wall thimble.
Install interior nished collar.
Install the vent section through the wall.
THIS UNIT MUST BE VENTED WITH A 36” (91 cm) SNORKEL KIT
IF UNIT IS RATED FOR 30,000 Btu/hr NG and 26,000 Btu/hr LP.
Seal around the vent terminal to the structure using a non
hardening mastic.
Also refer to INITIAL INSTALLATION - VENT CONFIGURATIONS AND RESTRICTOR
SETTINGS.
Initial Installation
QUALIFIED INSTALLERS ONLY