5.3. Overview DIP switch
Different modes are selectable by using the DIP-switch (mode changes work only,
when the power supply is turned off and on).
DIP 1 Off
Controller enable not inverted (terminals 15 and 16 must be connected,
for working motor in the wanted direction)
DIP 1 ON
Controller enable inverted (terminals 15 and 16 must not be connected,
for working motor in the wanted direction)
DIP 2 Off
Speed ref. enable not inverted (terminal 18 must be connected, for a
working ref. Speed value)
DIP 2 ON
Speed ref. enable inverted (terminal 18 must not be connected, for a
working ref. Speed value)
DIP 3 Off
Speed ref. value 0 to 5V/10V means motor voltage: 0 to + +12V/+24V
(motor voltage)
DIP 3 ON
Speed ref. value 0 to 5V/10V means motor voltage: -12V/-24V to
+12V/+24V (half speed value -> motor voltage=0VDC)
DIP 4 Off Ramp for motor voltage 1 sec., when DIP5 and DIP 6 are Off
DIP 4 ON Ramp for motor voltage 2 sec., when DIP5 and DIP6 are Off
DIP 5 Off Ramp for motor voltage 1 sec., when DIP4 and DIP6 are Off
DIP 5 ON Ramp for motor voltage 3 sec., when DIP4 and DIP6 are Off
DIP 6 Off Ramp for motor voltage 1 sec., when DIP4 and DIP5 are Off
DIP 6 ON Ramp for motor voltage 5 sec., when DIP4 and DIP5 are Off
DIP 7 Off Motor turns not off after 3 sec. on current limit (motor overload)
DIP 7 ON Motor turns off after 3 sec. on current limit (motor overload)
DIP 8 Off No function
DIP 8 ON No function