of material 1 and the gradual feed is allowed, go to program step 7
and the timer will be T3; If the gradual feed is not allowed and the
weight is more than the batching value plus tolerance, out-of
-tolerance treatment will stop at this step and wait for qualified
out-of-tolerance treatment. If the out-of-tolerance treatment is not
done, then go to program step 9, the timer will be T5.
7 Start the slow feed of material 1. When timing is over, the slow
feed will be closed and timer will be T4, then go to program step 8.
8 Treatment is same as the program step 6
9 If timing is over, the qualified or out-of-tolerance signal will be
shut down. If the batching value of material 2 is less than the scale
interval, go to program step 19, otherwise, go to program step 10.
10 Wait for the stable display light to be ON and tare to be
automatically done, timer will be T0 and go to program step 11.
11 Start the quick feed of material 2. If T0 is 0, start the slow feed of
material 2 at same time. When the timing of T0 is over, weight
inspection is started. If the loaded value reaches batching value of
material 2 minus quick feed lead of material 1, turn off quick feed
of material 2. The time will be T1 and go to program step 12.
12 Timing is over, go to program step 13 and the timer is T0.
13 Start the slow feed. The timing is over and weight inspection is
started. If the loaded value reaches to batching value of material 1
minus slow feed lead of material 2, turn off slow feed of material
2..Timer will be T2 and go to program step 14.
14 The timing is over. If the lead is allowed to correct, correct the
slow feed lead of material2, Go to program step 15.
15 If the material 2 weight is qualified, the qualified signal will be
output and it will go to program step 18, the timer will be T5. If it
is out of tolerance, output the out-of-tolerance signal. If the weight