Installation manual

630077_5 Outer Skin Kit Installation Manual.doc
12
10.3 Installing the Flue System AUSTRALIA ONLY:
Non-Masonry Timber Frame Cavity:
The heater must be flued to the outside via a 100mm diameter inner flue that is covered by a
150mm diameter liner. This must be installed in accordance with the requirements of
AS5601 and local codes.
The minimum flue length = 3.6m vertical height
10.4 AUSTRALIA ONLY Consult the installation instructions that come with your flue
kit. To ensure safety the flue kit must be installed according to those instructions. An
overview is provided below. Ensure all clearances to combustibles are maintained as per
specifications earlier in this manual.
It is important to check that you have all the necessary flue parts before beginning your
installation.
1. Locate the Outer Skin Kit in the cavity as per the instructions in section
15 of this manual. Mark the point for penetration that is directly above
the centre of the flue outlet on the gas fireplace. Check that the location
ensures that the flue outer liner maintains a 25mm clearance to all
combustibles and timber framing.
2. Cut a 200mm square hole where the penetration is required using the
mark created in step 1 as a guide. Fit non-combustible nogs in the
ceiling space if required.
3. Measure the overall flue length required. Remember to allow for all
necessary clearances to neighbouring structures (including a minimum
of 600mm clearance above the nearest point on any part of the roof). It
is recommended that extending the flue above the ridgeline will assist
with down draught issues. Consult AS5601 2002 for further information.
4. Assemble all the outer liner lengths and fix together with pop rivets or
self tapping screws. Lower the assembled outer liner through the roof (or
false chimney) and secure to the fixed part of the Outer Skin Kit. Fix as
necessary to inner framing where possible (see section 12.4).
5. Assemble the Ø100mm inner flue lengths using pop rivets or self tapping
screws. It is recommended that all flue joints are sealed. Lower the
Ø100mm inner flue assembly from the roof through the centre of the
outer liner and locate onto the gas fireplace spigot. Ensure that the top
of the Ø100mm inner flue is at the correct height at the top of the outer
liner.
Gas Cowl
Outer Liner Ø150mm
Ø100mm Inner Flue