FROM AS5601, please ensure compliance to all other relevant sections of this code.
2.6.13 FLUE TERMINALS
2.6.13.1 Location
The termination point of a flue shall be located in relation to any associated building and to
neighboring
structures so that wind from any direction is not likely to create a downdraught in the flue or
chimney.
Except where 2.6.13.3 applies, a flue terminal shall:
(a) Be at least 1m horizontally from a neighboring structure; or
(b) If less than 1m horizontally from a neighboring structure, be at least 500mm above that
structure;
(c) Be at least 1.5m from any opening into a building; and
(d) Be at least 200mm from another flue terminal.
2.6.13.2 Terminating a flue above a roof
Where a flue is to terminate above:
(a) A roof; the end of the flue shall be at least 500mm from the nearest part of the roof;
(b) A trafficable roof designed for personal or public use, the end of the flue shall be at least
2m above the roof level and at least 500mm above any surrounding parapet; or
(c) A chimney, the end of the flue shall be at least 200mm from the nearest part of the
chimney.
NOTE-
(1) The distance is measured before the cowl is fitted to the end of the flue
(2) (NA)
(3) (NA)
2.6.13.3 Location of a flue terminal other than above a roof
(NA)