Datasheet

Constant power discharge
1.75 Vpc – Discharge in W/block at 20 °C
Exide type
designation
Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1 h 1.5 h
A502/10 S NGA5020010HS0SA 60.0 58.0 45.0 36.0 30.0 22.0 17.0 14.0 10.0
A504/3.5 S NGA50403D5HS0SA 49.0 41.0 30.0 23.0 20.0 15.0 12.0 9.00 6.00
A506/1.2 S NGA50601D2HS0SA 25.1 20.7 14.0 11.1 9.30 7.00 5.20 4.20 3.00
A506/3.5 S NGA50603D5HS0SA 73.0 62.0 45.0 35.0 29.0 22.0 18.0 14.0 10.0
A506/4.2 S NGA50604D2HS0SA 89.0 77.0 52.0 40.0 36.0 31.0 17.0 15.0 11.0
A506/6.5 S NGA50606D5HS0SA 138 121 86.0 66.0 57.0 42.0 30.0 24.0 17.0
A506/10 S NGA5060010HS0SA 181 173 135 109 90.0 66.0 51.0 42.0 30.0
A508/3.5 S NGA50803D5HS0SA 97.0 82.0 60.0 46.0 39.0 29.0 23.0 18.0 13.0
A512/1.2 S NGA51201D2HS0SA 50.1 41.4 28.0 22.2 18.6 14.0 10.3 8.30 6.10
A512/2 S NGA5120002HS0SA 91.0 75.0 52.0 40.0 33.0 25.0 18.0 15.0 11.0
A512/3.5 S NGA51203D5HS0SA 146 123 89.0 69.0 59.0 44.0 35.0 27.0 19.0
A512/6.5 S NGA51206D5HS0SA 276 242 172 132 114 84.0 60.0 48.0 34.0
A512/10 S NGA5120010HS0SA 361 346 270 219 179 132 103 83.0 60.0
A512/16 G5 NGA5120016HS0BA 636 534 407 322 280 209 159 126 91.0
A512/25 G5 NGA5120025HS0BA 689 616 454 385 320 248 185 150 111
A512/30 G6 NGA5120030HS0BA 1118 951 690 538 453 341 271 214 153
A512/40 A NGA5120040HS0CA 1226 1074 822 691 569 432 326 261 189
A512/55 A NGA5120055HS0CA 1799 1496 1102 917 813 626 489 388 281
A512/60 A NGA5120060HS0CA 2267 1837 1274 1071 915 693 505 400 288
A512/65 A NGA5120065HS0CA 1757 1591 1223 1083 914 721 567 457 336
A512/85 A NGA5120085HS0CA 2561 2292 1847 1557 1329 1018 768 621 460
A512/115 A NGA5120115HS0CA 3642 3101 2374 1986 1653 1255 956 759 547
A512/120 A NGA5120120HS0CA 4237 3552 2627 2134 1800 1334 989 815 622
A512/140 A NGA5120140HS0CA 4647 3937 2912 2365 1995 1479 1096 904 689
A512/200 A NGA5120200HS0CA 5932 5092 3941 3201 2700 2002 1484 1223 933
1.70 Vpc – Discharge in W/block at 20 °C
Exide type
designation
Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1 h 1.5 h
A502/10 S NGA5020010HS0SA 64.0 60.0 46.0 38.0 31.0 22.0 17.0 14.0 10.0
A504/3.5 S NGA50403D5HS0SA 53.0 44.0 31.0 24.0 20.0 15.0 12.0 9.00 7.00
A506/1.2 S NGA50601D2HS0SA 26.8 21.9 14.4 11.2 9.40 7.10 5.20 4.20 3.10
A506/3.5 S NGA50603D5HS0SA 80.0 66.0 46.0 36.0 30.0 22.0 18.0 14.0 10.0
A506/4.2 S NGA50604D2HS0SA 97.0 81.0 54.0 41.0 36.0 32.0 17.0 15.0 11.0
A506/6.5 S NGA50606D5HS0SA 150 126 88.0 68.0 58.0 42.0 31.0 24.0 17.0
A506/10 S NGA5060010HS0SA 193 180 139 113 92.0 67.0 52.0 42.0 30.0
A508/3.5 S NGA50803D5HS0SA 106 88.0 61.0 48.0 40.0 30.0 24.0 19.0 13.0
A512/1.2 S NGA51201D2HS0SA 53.7 43.7 28.8 22.4 18.8 14.1 10.4 8.40 6.10
A512/2 S NGA5120002HS0SA 99.0 80.0 53.0 41.0 34.0 25.0 19.0 15.0 11.0
A512/3.5 S NGA51203D5HS0SA 159 131 92.0 72.0 60.0 45.0 35.0 28.0 20.0
A512/6.5 S NGA51206D5HS0SA 300 252 176 136 116 84.0 62.0 48.0 34.0
A512/10 S NGA5120010HS0SA 385 360 278 226 185 135 103 84.0 60.0
A512/16 G5 NGA5120016HS0BA 688 573 418 331 285 212 161 127 91.0
A512/25 G5 NGA5120025HS0BA 776 652 482 395 330 253 187 151 112
A512/30 G6 NGA5120030HS0BA 1214 1037 726 558 465 347 274 216 155
A512/40 A NGA5120040HS0CA 1391 1157 870 719 587 441 331 264 191
A512/55 A NGA5120055HS0CA 1912 1624 1163 935 834 636 493 392 283
A512/60 A NGA5120060HS0CA 2406 2022 1348 1088 940 707 514 405 290
A512/65 A NGA5120065HS0CA 1959 1739 1322 1142 954 739 577 464 340
A512/85 A NGA5120085HS0CA 2900 2486 1993 1607 1381 1045 786 634 469
A512/115 A NGA5120115HS0CA 4106 3361 2511 2030 1703 1281 971 770 553
A512/120 A NGA5120120HS0CA 4536 3800 2690 2201 1849 1365 1008 830 632
A512/140 A NGA5120140HS0CA 4974 4211 2981 2440 2050 1513 1117 920 700
A512/200 A NGA5120200HS0CA 6350 5446 4034 3302 2774 2048 1512 1245 948
Discharge datas are also valid for other terminals.
13