Datasheet

Constant power discharge
1.65 Vpc – Discharge in W/block at 20 °C
Exide type
designation
Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1 h 1.5 h
A502/10 S NGA5020010HS0SA 68.0 62.0 47.0 38.0 31.0 23.0 17.0 14.0 10.0
A504/3.5 S NGA50403D5HS0SA 57.0 46.0 31.0 24.0 20.0 15.0 12.0 9.00 7.00
A506/1.2 S NGA50601D2HS0SA 28.2 22.6 14.7 11.2 9.50 7.10 5.20 4.20 3.10
A506/3.5 S NGA50603D5HS0SA 85.0 68.0 47.0 36.0 30.0 23.0 18.0 14.0 10.0
A506/4.2 S NGA50604D2HS0SA 102 82.0 55.0 41.0 36.0 32.0 17.0 15.0 11.0
A506/6.5 S NGA50606D5HS0SA 160 129 90.0 69.0 59.0 43.0 31.0 25.0 18.0
A506/10 S NGA5060010HS0SA 205 186 142 114 93.0 68.0 52.0 42.0 30.0
A508/3.5 S NGA50803D5HS0SA 113 91.0 62.0 49.0 41.0 30.0 24.0 19.0 13.0
A512/1.2 S NGA51201D2HS0SA 56.4 45.3 29.4 22.5 18.9 14.2 10.5 8.40 6.10
A512/2 S NGA5120002HS0SA 103 82.0 54.0 41.0 34.0 25.0 19.0 15.0 11.0
A512/3.5 S NGA51203D5HS0SA 170 137 93.0 73.0 61.0 45.0 35.0 28.0 20.0
A512/6.5 S NGA51206D5HS0SA 320 258 180 138 118 86.0 62.0 50.0 36.0
A512/10 S NGA5120010HS0SA 410 371 283 229 187 136 104 84.0 61.0
A512/16 G5 NGA5120016HS0BA 741 601 423 335 288 213 161 128 92.0
A512/25 G5 NGA5120025HS0BA 854 693 501 400 335 255 188 152 112
A512/30 G6 NGA5120030HS0BA 1310 1095 746 569 471 351 276 217 155
A512/40 A NGA5120040HS0CA 1514 1235 902 729 597 446 333 265 192
A512/55 A NGA5120055HS0CA 2005 1726 1204 945 845 642 496 394 284
A512/60 A NGA5120060HS0CA 2548 2176 1404 1098 954 715 519 409 292
A512/65 A NGA5120065HS0CA 2139 1853 1395 1171 976 749 582 466 341
A512/85 A NGA5120085HS0CA 3115 2719 2109 1663 1410 1060 797 642 474
A512/115 A NGA5120115HS0CA 4304 3582 2603 2057 1732 1296 980 776 557
A512/120 A NGA5120120HS0CA 4847 4002 2761 2246 1883 1387 1022 843 640
A512/140 A NGA5120140HS0CA 5316 4435 3060 2489 2087 1538 1133 934 709
A512/200 A NGA5120200HS0CA 6786 5736 4142 3369 2825 2081 1533 1264 959
1.60 Vpc – Discharge in W/block at 20 °C
Exide type
designation
Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1 h 1.5 h
A502/10 S NGA5020010HS0SA 73.0 63.0 48.0 38.0 31.0 23.0 17.0 14.0 10.0
A504/3.5 S NGA50403D5HS0SA 59.0 46.0 32.0 25.0 20.0 15.0 12.0 9.00 7.00
A506/1.2 S NGA50601D2HS0SA 29.2 23.1 14.8 11.3 9.50 7.10 5.20 4.20 3.10
A506/3.5 S NGA50603D5HS0SA 89.0 69.0 47.0 37.0 31.0 23.0 18.0 14.0 10.0
A506/4.2 S NGA50604D2HS0SA 106 83.0 55.0 42.0 37.0 32.0 17.0 15.0 11.0
A506/6.5 S NGA50606D5HS0SA 168 132 92.0 70.0 59.0 43.0 31.0 25.0 18.0
A506/10 S NGA5060010HS0SA 218 190 144 115 94.0 68.0 52.0 42.0 30.0
A508/3.5 S NGA50803D5HS0SA 119 93.0 63.0 49.0 41.0 30.0 24.0 19.0 13.0
A512/1.2 S NGA51201D2HS0SA 58.4 46.2 29.7 22.5 19.0 14.2 10.5 8.40 6.20
A512/2 S NGA5120002HS0SA 106 84.0 55.0 42.0 34.0 25.0 19.0 15.0 11.0
A512/3.5 S NGA51203D5HS0SA 178 139 95.0 74.0 61.0 45.0 36.0 28.0 20.0
A512/6.5 S NGA51206D5HS0SA 336 264 184 140 118 86.0 62.0 50.0 36.0
A512/10 S NGA5120010HS0SA 437 381 287 231 188 136 104 85.0 61.0
A512/16 G5 NGA5120016HS0BA 783 621 426 338 289 214 162 128 92.0
A512/25 G5 NGA5120025HS0BA 908 725 514 403 339 256 189 153 113
A512/30 G6 NGA5120030HS0BA 1393 1121 755 576 474 352 276 218 156
A512/40 A NGA5120040HS0CA 1577 1299 923 735 603 449 334 266 192
A512/55 A NGA5120055HS0CA 2107 1800 1231 957 851 645 498 395 285
A512/60 A NGA5120060HS0CA 2680 2279 1439 1104 963 719 522 410 293
A512/65 A NGA5120065HS0CA 2315 1976 1443 1183 987 754 584 468 342
A512/85 A NGA5120085HS0CA 3264 2923 2190 1700 1427 1069 804 648 477
A512/115 A NGA5120115HS0CA 4467 3755 2665 2073 1750 1306 985 780 560
A512/120 A NGA5120120HS0CA 5135 4156 2812 2276 1906 1403 1032 852 646
A512/140 A NGA5120140HS0CA 5631 4606 3117 2522 2113 1555 1144 945 716
A512/200 A NGA5120200HS0CA 7189 5957 4218 3413 2860 2104 1548 1279 969
Discharge datas are also valid for other terminals.