Installation Guide

3
Section 2 Installation
2.1 Introduction to Installation
This EZ-Connect transfer switch has been wired and tested at the factory. Installing the switch
includes the following procedure:
Mounting the enclosure
Connecting utility and generator power source leads
Connecting the load leads
Installing/connecting any options and accessories
Testing the EZ-connect with portable generator
Carefully remove the EZ-Connect from carton and inspect device before installation. The purchaser
must file with carrier any claims for loss or damage incurred while in transit.
Features and Options of the EZ-Connect transfer Switch
The EZ-Connect transfer switch, housed in a NEMA 3R enclosure (Standard)
Power cord with the specified plug type on the end (Optional)
Surge Safe surge protection (Optional)
200 amp main breaker (Optional)
Instruction/operation manual
2.2 Tools Required
Flexible conduit, drill, drill bits, hole saw (type and length will be determined by material you will be
drilling and cutting), open ended wrenches or adjustable wrenches, socket wrenches, standard and
Phillips head screw drivers, sledge hammer, pencil, channel lock pliers, spade shovel, rake, screws,
nails, silicon caulk, and safety goggles.
2.3 Additional Equipment (Optional)
Post for mounting, post-hole digger, and cement.
2.4 Mounting
Mounting dimensions for EZ-Connect enclosure are located below. Find a suitable location to mount
the EZ-Connect transfer switch. The type 3R Enclosure is outdoor rated but can also be used for
indoor installation. Indoor installations however, may require additional wiring expenses. Mount the
switch vertically to a rigid supporting structure. To prevent switch distortion, level all mounting points.
Enclosure Dimensions
EZ-Connect
23x14.25x3.88
DANGER!
Verify both UTILTY and ALTERNATE power supplies
are OFF before trying to connect power source and
load lines to the EZ-Connect transfer switch. Supply
voltages are extremely high and dangerous. Move
handle on EZ-Connect into OFF position.
WARNING!
Power conductors and sending wires may have
voltage present that can cause severe personal injury
or death. De-energize all power or control circuit
conductors before beginning to perform any wiring
activity to or within the EZ-Connect transfer switch.