1-6 VersaMax System Genius® Network Interface Unit User's Manual November 2000 GFK-1535A
1
Genius NIU Specifications
Number of Modules 8 per rack, 64 per NIU/station
Network inputs per bus scan 128 bytes
Network outputs per bus scan 128 bytes
Discrete Input Memory 1024 points
Discrete Output Memory 1024 points
Analog Input Memory 64 channels
Analog Output Memory 64 channels
Power Consumption +5V@250mA, +3.3V@10mA
Serial Bus Address 0 to 31
Network data rate 153.6 Kbaud extended, 153.6 Kbaud
standard, 76.8 Kbaud, or 38.4 Kbaud.
Genius NIU Compatibility
Network Interface Unit IC200GBI001 is compatible with:
For a Series 90
-70 PLC
CPU firmware, release 3.0 or later.
Bus controller release 5.4 or later.
If the IC641SWP701/704 programming and configuration software is
used, it must be release 3.0 or later:
For a Series 90
-30 PLC
CPU firmware: any version. For expansion compatibility for CPUs
350, 352, 360, 363, and 364, version 10.0 or later is needed. Versions
earlier than 10.0 of any Series 90-30 CPU will go to Stop/Faulted
mode if an Add/Loss of Rack (expansion) fault is logged.
Bus Controller: any version.
For a Series Six
PLC:
CPU: rev. 105 or later
Programming Software: Release 4.02 or later
Bus controllers: IC660CBB902 or 903, version 1.7 or later