5. Commissioning
5−21
Festo P.BE−GDCP−SFC−LACI−PB−EN en 0812NH
5.2.9 Setting the PROFIBUS address
Permitted station numbers: 0 ... 125.
The invalid station number 255 is preset.
This is to make sure that a correct address is set during
commissioning or exchange.
Addresses cannot be assigned by the master
(the service Set_Slave_Address is not supported).
1. Select [Settings] [PB parameter] [PROFIBUS ADR]
(see also section 4.5.6).
2. The current
address is displayed with <Enter>.
3. Set the desired address with the arrow buttons.
4. Accept the address with OK <Enter>.
The set address becomes effective immediately and is
saved against network failure.
} Settings
PB parameter
PROFIBUS ADR
PROFIBUS Address
7
ESC <Menu>
Ok <Enter>