Instruction Manual

5. Commissioning
5−25
Festo P.BE−GDCP−SFC−LACI−PB−EN en 0812NH
Device control
When the SFC−LACI is switched on, the controller interface is
activated as standard [HMI = off].
Caution
Unexpected movements of the drive due to incorrect
parametrising
· Make sure that there is no active ENABLE signal when
switching on the SFC−LACI on the controller interface.
· Parameterise the entire system completely before
activating the controller with ENABLE (controller
interface), Enable" (FCT), or [HMI = on] (control panel).
In order that the FCT can control the connected SFC−LACI, the
SFC−LACI’s controller interface must be deactivated and
Controller enable" for the FCT must be set (FCT/HMI = on).
The actual status of
the control bit ENABLE then has no effect.
· To do this, go to the Project output" window, select the
Operate" tab and ,under Device Control", activate the
FCT" checkbox.
The controller interface of the SFC−LACI will then be
deactivated and Control Enable will be set for the FCT.