5. Commissioning
5−26
Festo P.BE−GDCP−SFC−LACI−PB−E N en 0812NH
5.4 Overview of commissioning on the PROFIBUS
The following steps are required for commissioning the
SFC−LACI as a field bus participant:
1. Set the PROFIBUS address of the SFC−LACI:
· on the control panel (only with type SFC−LACI−...−H2,
see section 5.2.9), or
· with the Festo Configuration Tool (see help for the
Festo Configuration Tool).
Permitted address range: 0 ... 125
Modification by a DP master is not possible.
2. Install the GSD file and icon file, see section 5.5.1.
3. Configure the PROFIBUS master with the relevant
configuration software (e.g. with STEP 7 Hardware
Configuration), see section 5.5.3.
4. Test
the field bus connection in online mode.
Details can be found in the following sections.