Parameter / Description CIFCTPNU
Out2: Setting condition rising/falling
Value = 0: The output is set if the reference value accrued from lower
values has been reached in accordance with 2422/04h.
Value = 1: The output is set if the reference value accrued from higher
values has been reached in accordance with 2422/04h.
1255 x 2422/06h
Out2: Resetting condition rising/falling
Value = 0: The output is reset if the reference value accrued from lower
values has been reached in accordance with 2422/05h.
Value = 1: The output is reset if the reference value accrued from
higher values has been reached in accordance with 2422/05h.
1256 x 2422/07h
Out2: Delay
Delay time in [ms] after a resetting condition has occurred. The output is
not reset until the delay time has expired (= switch−off delay).
1257 x 2422/08h
Out2: Inverted
0 = not inverted
1 = inverted
This setting is not taken into account when the output is used for a
brake/clamping unit (see 2422/01h).
1258 x 2422/09h
Out2: PWM value
Duty cycle during a period of time; see Fig.5/12
Values: 1 ... 100 %
Value = 0 deactivates the pulse−width modulation
1259 x 2422/0Ah
Tab.5/24: Parameters for the local digital outputs