3.7 Connecting the field bus
3.7.1 Field bus cable
Note
Faulty installations or high transmission rates may cause
data transmission errors as a result of signal reflections
and attenuations.
Transmission errors can be caused by:
missing or incorrect terminating resistor
incorrect screened connection.
branches
transmission over long distances.
unsuitable cables.
Observe the cable specifications. Refer to the manual for
your control system for information on
the type of cable to
be used.
Note
If the SFC−LACI is installed in a machine on a movable
mounting, the field bus cable must be provided with strain
relief on the moving part of the machine. Please also
observe the relevant regulations in EN60204 part 1.
Use a twisted screened 2−core cable for the field bus in
accordance with PROFIBUS
specifications (EN 50170,
cabletype A):
Surge impedance: 135 ... 165 (3 ... 20 MHz)
Capacitance per unit length: < 30 nF/km
Loop resistance: < 110 /km
Core diameter: > 0.64 mm
Wire cross section: > 0.34 mm
2