Instruction Manual

4. Control panel (only type SFC−LACI−...−H2)
4−15
Festo P.BE−GDCP−SFC−LACI−PB−EN en 0812NH
4.5.3 [Settings] [Homing paramet.]
Setting the homing method and the speed during reference
travel.
· Observe the instructions in section 5.2.1.
[Hom. paramet.]
Param. Description
[Homing method] switch negative Homing to the integrated
reference switch at the
retracted end position with
index search
block negative Homing to a negative
fixedstop
block positive Homing to positive
fixedstop
Note:
Further homing run methods can only be
configured via FCT.
[Velocity v_rp] v_rp Speed for searching for the
reference point
[Velocity v_zp] v_zp Speed for moving to the
axis zero point
[SAVE...] Save parameters in EEPROM
Note
A new homing run must always be carried out after
modifying the homing run method.
The maximum speed for homing is subject to built−in limits.