User Manual

4. Control panel (only type SFCLACI...H2)
4−17
Festo GDCP−SFCLACIDN−EN en 0812NH
4.5.5 [Settings] [Jog mode]
You can use the arrow keys to move the drive continuously
(also possible without previous reference run). The software
end positions have
no effect here.
4.5.6 [Settings] [BUS parameter]
Setting the field bus parameters
[BUS parameter]
Param. Description
[MAC ID] 0 ... 63
(0 ... 3Fh)
Field bus address of the SFCLACI
Representation: 00 dec, 00 hex"...63 dec, 3F hex"
[Baudrate] 125 kBd
250 kBd
500 kBd
Field bus baud rate as per settings on master
[I/O Datalength] 8 / 16bytes Set I/O data length
8 bytes:
only FHPP standard (the SFCLACI is controlled as per the
Festo Handling and Positioning Profile)
16 bytes:
FHPP standard and FPC (additional use of the FPC for
parameterising the SFCLACI)
Tab.4/6:Menu [Settings] [BUS parameter]
The settings in this menu will be saved directly in EEPROM
where they are safe from poweer failures after confi
rmation
with OK <Enter>.
Note
The set field bus parameters first become effctive aft er
Power off/on" or after a software reset (object 20F1/03h).