User Manual

5. Commissioning
59
Festo GDCP−SFCLACIDN−EN en 0812NH
5.2.1 Set the field bus parameter
· Switch the SFCLACI on. During first commissioning or
when the EEPROM has been deleted, the error message
DeviceNet INIT PARAMETER ERROR" will appear.
In
order to set the field bus parameters during first
commissioning or after deletion of the EEPROM:
· Select Config <Enter>.
For modifying the field bus parameters when recommisioning
(i.e. when these parameters have already been completely
parameterised
once):
· Select [Settings] [BUS parameter] [...]
(see also section 4.5).
1. Select the desired field bus parameter with the arrow
keys (details see next page).
2. Pr
ess <Enter> to display the current setting.
3. If necessary, modify the setting with the arrow keys.
4. Accept the setting with OK <Enter>. The setting i
s saved
against network failure.
Note
The set field bus parameters first become effctive aft er
Power off/on" or after a software reset
(object 20F1/03h / PNU 127).
DeviceNet INIT
PARAMETER ERROR
Diagnostic <menu>
Config <Enter>
SFC–LACI...
D...
Xa = 0.00 mm
HMI:off
<Menu>
DeviceNet
MAC ID
Baudrate
I/O Datalength
ESC <Menu>
<–> OK <Enter>