5. Commissioning
510
Festo GDCP−SFCLACIDN−EN en 0812NH
Station number (MAC ID)
Permitted station numbers: 0 ... 63
An invalid station number is preset (shown on control
panel as ???").
This is to make sure that a correct address is set dur
ing
commissioning or exchange.
Baudrate (baud rate)
Possible baud rates: 125, 250, 500 kBd
An invalid baud rate is preset (shown on control panel as
???").
This is to make sure that a correct baud is set during
comm
issioning or exchange.
I/O Datalength (data length)
The following settings are possible:
8 bytes:
FHPP standard (control of the SFCLACI takes place
according to Festo Handling and Positioning Profile)
16
bytes:
FHPP standard and FHPP−FPC (additional use of the
FPC for parameterising the SFCLACI). It is transmitted
in 3 telegrams.
An invalid data length is preset
(displayed as ???" on the
control panel). This is to make sure that the correct data
length is set during commissioning or exchange.
} Settings
BUS parameter
MAC ID
DeviceNet MAC ID
06 dec, 06 hex
ESC <Menu>
<––> OK <Enter>
} Settings
BUS parameter
Baudrate
BUS Baudrate
125 kBd
ESC <Menu>
<––> OK <Enter>
} Settings
BUS parameter
I/O Datalength
I/O Datalength
08 byte
ESC <Menu>
<––> OK <Enter>