User Manual

5. Commissioning
575
Festo GDCP−SFCLACIDN−EN en 0812NH
Overview of parameters involved (see section B.4.9)
Parameter Description FCT PNU CI
Setpoint position 1040 6062h
Actual position 1041 6064h
Standstill position window 1042 2040h
Standstill monitoring time 1043 2041h
Start (FHPP) SPOS.B2 = positive edge: Motion Complete
Feedback (FHPP) SPOS.B6 = 1: drive has moved out of standstill position window
Prerequisites Device control by PLC/field bus
Controller must be in status Operation enabled"
Tab.5/20: Parameters involved in standstill monitoring