User Manual

B. Parametrizing via field bus
B−52
Festo GDCP−SFCLACIDN−EN en 0812NH
DeviceNet Diagnosis
PNU 206 1 ... 6 Array uint8 r
Description Read out the field bus diagnostic data
Network Status 206 1
0x00: Bus is inactive, missing bus power supply
0x01:Serious error
0x04/5: Error can be rectified (e.g. Timeout)
0x10: Active connection with DeviceNet Master
0x20: Device self test
0x40/50:No connection to DeviceNet Master
Baudrate 206 2
Baud rate Values: 0 ... 2 Z 125, 250, 500 kBaud
0xFF Z invalid baud rate
206 3
(reserved)
MAC ID 206 4
Values: 0 ... 63 (0x00 ... 0x3F)
I/O Datalength 206 5
0x10: 8 bytes I/O data length (FHPP standard)
0x11: 16 bytes I/O data length (FHPP + FPC)
206 6
(reserved)
CI 2FF4h 01h ... 06h uint8 r
DeviceNet C: 109 A: 1, 2, 4, 5 I: 1 uint8 r