B. Parametrizing via field bus
B−76
Festo GDCP−SFCLACIDN−EN en 0812NH
Position Window Time
PNU 415 1 ... 33
d
uint16 rw
Description Damping time in milliseconds [ms].
If the actual position has been in the target position window for this
amount of time, the Motion Complete" bit is set in the status word.
Also referred to as Adjustment time".
Value range: 1 ... 60000 ms
Default: 10 ms
Record 0
(Positioning Record 0)
415 1
(Positioning Record 0)
Do not use (Homing)
Record ...
(positioning record )
415 ...
(positioning record ...)
Damping time for positioning records 1 ... 30
Record 31
(positioning record 31)
415 32 (20h)
(positioning record 31)
Damping time for position record 31
Jog Mode 415 33 (21h)
Damping time with jog mode
CI 20E6h 01h ... 22h uint16 rw
Subindex 20E6/22h: } PNU 1023
(damping time for positioning in direct mode)
Note: The object 20E0h/07h is provided for access via CI.
6068h contains the damping time of the currently active record.
DeviceNet C: 104 A: 14 I: 1 ... 33 uint16 rw