Special features of homing
To reference switch If a reference signal is not found when homing to the
reference switch before the drive reaches a
fixed stop or a
limit switch, then the drive will reverse and search for the
switch in the opposite direction. If a refer
ence signal is found
there, the drive runs through the switching range of the
reference switch. The reference point is subsequently the
follo
wing index pulse at the end of the switching range.
To limit switch If a reference signal is not found when homing to the limit
switch before the drive reaches a fixed stop, then homing is
interrupted and a homing error is registered.
Note
Homing error due to incorrect positioning of the limit
switches
· Position the limit switches such that the switching range
extends over the nearest fixed stop (or end position).
There must no range b
etween the limit switch and fixed
stop (or end position) in which the limit switch is not
actuated (undefined range).
· Note that ferritic elements (e.g.mounting attachments)
in the vicinity of magnetic switches can move the
switching range.