A. Technical appendix
A−21
Festo P.BE−SFC−DC−PB−S7−EN en 0604NH
A.2.7 Standstill monitoring
With the standstill monitoring it is clear that the target
position window is exited at a standstill.
When the target position is reached and the MC signal is
registered the drive enters the Standstill" status, the bit
Standstill_Control is reset. If, in this status, the drive is
removed from the standstill position window
for a minimum
defined time due to external forces or other influences, the bit
Standstill_Control will be set.
As soon as the drive is in the standstill position window again
for the standstill monitoring time, the bit Standstill_Control
will be reset.
1 Target position
2 Actual position
3 Standstill monitoring
(Standstill_Control)
4 Motion Complete
(MC)
5 Standstill position
window
6 Target position
window
7 Monitoring time
(position window
time)
8 Standstill monitoring
time
1
0
1
0
1
2
3
4
56
7
88
Fig.A/7: Standstill monitoring
The standstill monitoring cannot be switched on or off ex
plicitly. It becomes inactive when the standstill position win
dow is set to the value 0".