Manual

4. Parametrizing blocks
4−16
Festo P.BE−SFC−DC−PB−S7−EN en 0604NH
4.5 Fault information
A distinction is always made between two types of faults:
block faults and transmission faults.
Block faults (e.g. incorrect logic address, incorrect hardware
configuration, etc.) are caused by the relevant system func
tion blocks used SFC14/SFC15, SFC58/SFC59, SFB52/SFB53
or SFC24 and shown at the output RET_VALUE. The fault code
can be found in the
STEP 7 help. If a block fault occurs, the
block will be exited with the ENO bit = 0.
Transmission faults arise as a result of incorrect parameter
data (e.g. non−existent PN U, incorrect parameter length when
writing, non−existent subindex, etc.).
Transmission faults are shown with the bit Fault.
With the aid of the
value of Value_RD the fault can be evalu
ated accordingly Tab.4/10.
Fault numbers
Description
0 0x00 Non−permitted PNU The parameter does not exist.
1 0x01 Parameter value cannot be modified (read only)
(2) 0x02 (reserved lower or upper limit value exceeded)
1)
3 0x03 Faulty subindex
4 0x04 No array
5 0x05 Incorrect data type
(6) 0x06 (reserved setting not permitted can only be reset)
1)
(7) 0x07 (reserved describing element cannot be modified)
1)
(8) 0x08 (reserved PPO−Write requested in IR does not exist)
1)
9 0x09 Description data do not exist
(10) 0x10 (reserved access group incorrect)
1)
11 0x0A No control sovereignty
(12) 0x0B (reserved password incorrect)
1)
1)
These fault numbers are not used