Data Sheet

E
Functions for 72.01 and 72.11
U = Supply voltage
B1 = Max level
electrode
B2 = Min level
electrode
B3 = Common
= Contact 11-14
Z1-Z2 = Link to select
emptying
(Type 72.11)
LED
Supply
voltage
NO output
contact
Contacts
Open Closed
OFF Open 11 - 14 11 - 12
ON Open 11 - 14 11 - 12
ON
Open
(Timing in Progress)
11 - 14 11 - 12
ON Closed 11 - 12 11 - 14
Function and Run-on time
Type 72.01 Type 72.11
FL = Level control by Filling, Long (7
s) run-on delay. F = Level control by Filling, Z1–Z2 open. Run-on time fixed at 1s.
FS = Level control by Filling, Short (0.5
s) run-on delay. E = Level control by Emptying, Z1–Z2 linked. Run-on time fixed at 1s.
ES = Level control by Emptying, Short (0.5
s) run-on delay.
EL = Level control by Emptying, Long (7
s) run-on delay.
Filling functions
Wiring diagram Examples with 3 electrodes
Type 72.01
U = 24VDC
24VAC 50/60Hz
(110…125)VAC 50/60Hz
(230…240)VAC 50/60Hz
Type 72.11
F = Filling
Level
Filling Control – between Min. and
Max. levels.
Under normal operation the liquid
level can be expected to cycle
between the Minimum and the
Maximum electrodes, B2 and B1
(plus a degree of over and under-
shoot).
Switch On:
On “power-up, if the liquid is
below B1 the output relay will
operate after time T has expired.
On the liquid level falling below
B2, the output relay will operate
after time T has expired.
Switch Off:
On the liquid level reaching
electrode B1, the output relay
will de-energise after time T has
expired.
On “power-off, the output relay
will immediately de-energise.
Wiring diagram Examples with 2 electrodes
Type 72.01
U = 24VDC
24VAC 50/60Hz
(110…125)VAC 50/60Hz
(230…240)VAC 50/60Hz
Type 72.11
F = Filling
Level
Filling Control – about a single
level, B1.
Under normal operation the liquid
evel can be expected to cycle about
the level set by electrode B1 with a
degree of over and under-shoot.
Switch On:
On “power-up, if the liquid is
below B1 the output relay will
operate after time T has expired.
On the liquid level falling below
B1, the output relay will operate
after time T has expired.
Switch Off:
On the liquid level reaching
electrode B1, the output relay will
de-energise after time T has expired.
On “power-off, the output relay
will immediately de-energise.