Datasheet

X-2017, www.findernet.com
I
Relays for automatic control of lighting
according to the ambient light level
Integral light sensor
For pole or wall mounting
10.32 - 2 NO 16A output contacts
10.41 - 1 NO 16A output contact
Double pole Live and Neutral switching
possible with the 10.32
Sensitivity adjustment from 1 to 80lux
Cadmium free contact material
Cadmium free light sensor (IC photo diode)
Electronic circuit - transformer isolated
Italian Patent “light feedback compensation
innovative principle
Compatible with slow starting gas discharge
lamps (up to 10minutes)
For the first 3 working cycles the delay time
(On and Off) is reduced to zero in order to aid
installation
Available for supply 230 and 120VAC
(50/60Hz)
10.32 10.41
Double pole switching - 2NO
16A for Live and Neutral
switching
Single pole switching - 1NO
16A for Live switching
For outline drawing see page 8
Contact specification
Contact configuration 2 NO (DPST-NO) 1 NO (SPST-NO)
Rated current/Maximum peak current A 16/30 (120A - 5ms) 16/30 (120A - 5ms)
Rated voltage/
Maximum switching voltage VAC 120/— 230/— 120/— 230/—
Rated load AC1 VA 1900 3700 1900 3700
Rated load AC15 VA 400 750 400 750
Rated current AC5a A 5 5
Nominal lamp rating:
230V incandescent/halogen W 2300 2000
fluorescent tubes with
electronic ballast W 600 1200 500 1000
fluorescent tubes with
electromechanical ballast W 450 850 400 750
CFL W 250 500 200 400
230V LED W 500 400
LV halogen or LED with
electronic ballast W 250 500 200 400
LV halogen or LED with
electromechanical ballast W 500 1000 400 800
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Standard contact material AgSnO
2
AgSnO
2
Supply specification
Nominal voltage (U
N
) VAC (50/60Hz) 120 230 120 230
VDC
Rated power AC/DC VA (50Hz)/W 2/— 2/—
Operating range AC (50Hz) (0.8…1.1)U
N
(0.8…1.1)U
N
DC
Technical data
Electrical life at rated load in AC1 cycles 100·10
3
100·10
3
Threshold setting lx 1…80 1…80
Preset threshold lx 10 10
Delay time: switching ON/OFF s 15/30 15/30
Ambient temperature range °C –30…+70 –30…+70
Protection category IP 54 IP 54
Approvals (according to type)
3
10
SERIES
10 SERIES
Light dependent relays 12 - 16A