Relays for automatic control of lighting
according to the ambient light level
Integral light sensor
For pole or wall mounting
10.42 - Two independent 16A outputs with
individual lux setting
10.51 - Miniature single 12A1 NO output
10.61 - Mounting on street light body
Sensitivity adjustment from 1 to 80lux
Fixed sensivity 10lux (±20%) - (10.61 type)
Cadmium free contact material
Cadmium free light sensor (IC photo diode)
Electronic circuit - transformer isolated
(10.42type)
Italian Patent “light feedback compensation
innovative principle (10.51type)
For the first 3 working cycles the delay time
(On and Off) is reduced to zero in order to aid
installation
Available for supply 230 and 120VAC
(50/60Hz)
Prewired with silicone wire, 500mm length
(10.61type)
10.42 10.51 10.61
Two independent outputs -
2NO16A
Single pole switching -
1NO12A
Miniature size
Single pole switching -
1NO16A
For outline drawing see page 8
Contact specification
Contact configuration 2 NO (DPST-NO) 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current/Maximum peak current A 16/30 (120A - 5ms) 12/25 (80A - 5ms) 16/30 (120A - 5ms)
Rated voltage/
Maximum switching voltage VAC 120/— 230/— 120/— 230/— 230/—
Rated load AC1 VA 1900 3700 1400 2760 3700
Rated load AC15 VA 400 750 300 600 750
Rated current AC5a A 5 5
Nominal lamp rating:
230V incandescent/halogen W 2000 1200 2000
fluorescent tubes with
electronic ballast W 500 1000 300 600 1000
fluorescent tubes with
electromechanical ballast W 400 750 200 400 750
CFL W 200 400 200 350 400
230V LED W 400 350 400
LV halogen or LED with
electronic ballast W 200 400 200 350 400
LV halogen or LED with
electromechanical ballast W 400 800 300 600 800
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10) 1,000 (10/10)
Standard contact material AgSnO
2
AgSnO
2
AgSnO
2
Supply specification
Nominal voltage (U
N
) VAC (50/60Hz) 120 230 120 230 230
VDC
Rated power AC/DC VA (50Hz)/W 2/— 1.5/— 2.5/—
Operating range AC (50Hz) (0.8…1.1)U
N
(0.8…1.1)U
N
(0.8…1.1)U
N
DC
Technical data
Electrical life at rated load in AC1 cycles 100·10
3
100·10
3
100·10
3
Threshold setting lx 1…80 1…80 10
Preset threshold lx 10 10 10
Delay time: switching ON/OFF s 15/30 15/30 15/30
Ambient temperature range °C –30…+70 –30…+70 –30…+70
Protection category IP 54 IP 54 IP 54
Approvals (according to type)
4
10 SERIES
Light dependent relays 12 - 16A
10
SERIES