Data Sheet
XI-2017, www.findernet.com
9
I
12
SERIES
12 SERIES
Time switches 16A
Technical data
Insulation 12.51, 12.61, 12.62, 12.81,
12.A1, 12.A2
12.01, 12.11, 12.31, 12.71
Dielectric strength between supply and contacts VAC 4000 4000
Dielectric strength between open contacts VAC 1000 1000
Rated impulse voltage (between supply and contacts) kV/(1.2/50)μs 6 6
Rated impulse voltage (between open contacts) kV/(1.2/50)μs 1.5 1.5
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN61000-4-2 4kV 6kV
air discharge EN61000-4-2 8kV 8kV
Radiated electromagnetic field (80…1000MHz) EN61000-4-3 10V/m 10V/m
Fast transients (burst 5/50ns, 5 and 100kHz) EN61000-4-4 4kV 4kV
Voltage pulses on supply
terminals (surge 1.2/50μs)
common mode EN61000-4-5 4kV 2kV
differential mode EN61000-4-5 4kV 2kV
Radiofrequency common mode voltage (0.15…80MHz) EN61000-4-6 10V 10V
Voltage dips 70%U
N
, 40%U
N
EN61000-4-11 10 cycles 10 cycles
Short interruptions EN61000-4-11 10 cycles 10 cycles
Radio frequency conducted emissions 0.15…30MHz EN55014 class B class B
Radiated emissions 30…1000MHz EN55014 class B class B
Terminals
Screw torque Nm 0.8 1.2
Max. wire size mm
2
AWG mm
2
AWG
solid cable 1x6/ 2x4 1x10/ 2x12 1x6/ 2x4 1x10/ 2x12
stranded cable 1x4/ 2x2.5 1x12/ 2x14 1x6/ 2x2.5 1x10/ 2x14
Wire strip length mm 9
Other data
Power back-up (Battery life) 6 years (12.51, 12.61, 12.62, 12.81, 12.A1, 12.A2, 12.71)
Battery type CR2032, 3V, 230mAh (12.51, 12.61, 12.62, 12.81, 12.A1, 12.A2)
Power back-up 100h (12.01, 12.11, 12.31 - following 80h continuous energisation)
Power lost to the environment
12.51, 12.61,
12.81, 12.A1
12.62, 12.A2 12.01, 12.11,
12.31
12.71
in stand-by W 0.2 0.2 — —
without contact current W 0.9 0.9 1.5 2
with rated current W 1.5 2.1 2.5 3 (for 1 pole)
L 12 - Rated current v ambient temperature
1 pole
2 pole