Dimmers
15
SERIES
Signaling
LED (15.10 only) Condition LED (15.11 only) Condition
Stand-by, output voltage <1V Stand-by, input voltage <1V
Active, output voltage ≥1V Active, input voltage ≥1V
Timing, staircase function
Short circuit or overload,
output disabled
Overtemperature, output disabled
Functions - Type 15.10 and 15.11
Type Linear dimming
15.10
Operating mode without memory: at switch-off, the light level is not memorized.
Long control pulse: The light level is progressively raised or lowered in linear way
.
The
lowest value depending on the “minimum dimming level” regulator setting (on 15.11).
Short control pulse: Alternately switches between On and Off (maximum light
level and the off state).
Operating mode with memory: the previous light level is memorized.
Long control pulse: The light level is progressively raised or lowered in linear
way. The
lowest value dependent on the “minimum dimming level” regulator setting (on 15.11).
Short control pulse: Alternately switches between On and Off. When switching
On, the light level assumes the value set during the previous On state.
Operating mode with memory: the previous light level is memorized, specific
for CFL Lamp.
Long control pulse: The light level is progressively raised or lowered in linear way.
The
lowest value dependent on the “minimum dimming level” regulator setting
(on 15.11).
Short control pulse: Alternately switches between On and Off. When switching On,
the light level reach the full value for a very short time (in order to guarantee the correct
lamp turn-on), then immediately assumes the value set during the previous On state.
Staircase relay with early warning
On initial impulse the output closes and the timing starts for the pre-set duration.
After the timing period (T), the output power is reduced to 50% for 10seconds;
then in the last 30seconds it will be further reduced to the
final shutdown.
During the pre-set and 40seconds warning time, it is possible, by a further impulse, to
extend the time by the full pre-set value.
Type of load - Type 15.11
Type of load
Selector
setting
Regulator setting
Incandescent lamps
230V halogen lamps
12/24V halogen and LED lamps with electronic
transformer/ballast
(Trailing Edge)
It is suggested to set the “minimum dimming level”
at the lowest value, so that the complete dimming
range is available. But if it is necessary to avoid too
low a level of illumination, a higher value can be set.
Dimmable compact fluorescent lamps (CFL)
Dimmable LED lamps
(Leading Edge)
It is suggested to initially set the “minimum
dimming level” at an intermediate value and
then if necessary, readjust for a level found to be
compatible with the lamp being used.
12/24V halogen lamps with toroidal or E-core
electromagnetic transformer
(Leading Edge)
It is suggested to set the “minimum dimming level”
at the lowest value, so that the complete dimming
range is available. But if it is necessary to avoid too
low a level of illumination, a higher value can be set.